Voltage Drop Calculator

HomeVoltage drop

277 volt voltage drop calculator

277 V is the line-to-neutral voltage of a 277/480 V system, used for commercial lighting. The higher voltage lets lighting circuits run several hundred feet. Enter your wire size, load and distance.

V
A
One way, from the source to the load.
3% for a branch circuit or feeder is the NEC informational guideline.
%

Voltage drop

Fill in the circuit, then press the button.

Volts allowed at 277 V

Target1%2%3%5%
Volts lost2.8 V5.5 V8.3 V13.8 V

At 277 V, the NEC's 3% suggestion means losing no more than 8.3 V between the panel and the load, leaving 268.7 V at the equipment.

Maximum one-way distance at 3%, 277 V single-phase

Load12 AWG10 AWG8 AWG6 AWG
15 A139 ft223 ft356 ft564 ft
20 A104 ft167 ft267 ft423 ft
30 A—111 ft178 ft282 ft

Copper, 75 °C ampacity. A dash means the wire is too small for that current. For aluminum, multiply each distance by about 0.61.

Drop on 12 AWG at 16 A

One-way lengthDropDrop %At the load
25 ft1.58 V0.57%275.4 V
50 ft3.17 V1.14%273.8 V
100 ft6.34 V2.29%270.7 V
150 ft9.50 V3.43%267.5 V
200 ft12.67 V4.57%264.3 V
300 ft19.01 V6.86%258.0 V

R is the conductor resistance in ohms per 1,000 ft (NEC Chapter 9, Table 8), L is the one-way length in feet and I is the load current in amps. The 2 counts the wire out and the wire back; on three-phase circuits the return current is shared, so the factor becomes √3, or 1.732.

Common questions

Do I enter the one-way length or the total wire?

Enter the one-way distance from the panel or source to the load. The calculator doubles it for the out-and-back path on single-phase and DC circuits, and applies the 1.732 factor for three-phase.

Is 3% voltage drop a code requirement?

Not in most cases. The NEC puts the 3% branch-circuit and 5% total figures in informational notes, which explain good practice but are not enforceable on their own. A few sections do set hard limits, such as 647.4(D) for sensitive electronic equipment and 695.7 for fire pumps, and some energy codes and job specifications make 3% or 5% mandatory.

How far can I run 10 AWG at 277 V?

At 15 A, 10 AWG copper reaches about 223 ft one way before the drop passes 3%. Double the current and the distance halves.

Sources

  • NFPA 70, National Electrical Code, 2023 edition (https://www.nfpa.org/codes-and-standards/nfpa-70-standard-development/70)