277 volt voltage drop calculator
277 V is the line-to-neutral voltage of a 277/480 V system, used for commercial lighting. The higher voltage lets lighting circuits run several hundred feet. Enter your wire size, load and distance.
Voltage drop
Fill in the circuit, then press the button.
Volts allowed at 277 V
| Target | 1% | 2% | 3% | 5% |
|---|---|---|---|---|
| Volts lost | 2.8 V | 5.5 V | 8.3 V | 13.8 V |
At 277 V, the NEC's 3% suggestion means losing no more than 8.3 V between the panel and the load, leaving 268.7 V at the equipment.
Maximum one-way distance at 3%, 277 V single-phase
| Load | 12 AWG | 10 AWG | 8 AWG | 6 AWG |
|---|---|---|---|---|
| 15 A | 139 ft | 223 ft | 356 ft | 564 ft |
| 20 A | 104 ft | 167 ft | 267 ft | 423 ft |
| 30 A | — | 111 ft | 178 ft | 282 ft |
Copper, 75 °C ampacity. A dash means the wire is too small for that current. For aluminum, multiply each distance by about 0.61.
Drop on 12 AWG at 16 A
| One-way length | Drop | Drop % | At the load |
|---|---|---|---|
| 25 ft | 1.58 V | 0.57% | 275.4 V |
| 50 ft | 3.17 V | 1.14% | 273.8 V |
| 100 ft | 6.34 V | 2.29% | 270.7 V |
| 150 ft | 9.50 V | 3.43% | 267.5 V |
| 200 ft | 12.67 V | 4.57% | 264.3 V |
| 300 ft | 19.01 V | 6.86% | 258.0 V |
R is the conductor resistance in ohms per 1,000 ft (NEC Chapter 9, Table 8), L is the one-way length in feet and I is the load current in amps. The 2 counts the wire out and the wire back; on three-phase circuits the return current is shared, so the factor becomes √3, or 1.732.
Common questions
Do I enter the one-way length or the total wire?
Enter the one-way distance from the panel or source to the load. The calculator doubles it for the out-and-back path on single-phase and DC circuits, and applies the 1.732 factor for three-phase.
Is 3% voltage drop a code requirement?
Not in most cases. The NEC puts the 3% branch-circuit and 5% total figures in informational notes, which explain good practice but are not enforceable on their own. A few sections do set hard limits, such as 647.4(D) for sensitive electronic equipment and 695.7 for fire pumps, and some energy codes and job specifications make 3% or 5% mandatory.
How far can I run 10 AWG at 277 V?
At 15 A, 10 AWG copper reaches about 223 ft one way before the drop passes 3%. Double the current and the distance halves.