48 volt DC voltage drop calculator

48 V DC is the standard for off-grid solar battery banks, telecom and server racks. Lower current means smaller cable between the battery, inverter and charge controller. Enter the wire gauge, current and one-way length.

V
A
One way, from the source to the load.
3% for a branch circuit or feeder is the NEC informational guideline.
%

Voltage drop

Fill in the circuit, then press the button.

Wire gauge for 48 V at 3% drop

Smallest copper size that holds the drop to 3% (1.44 V). Lengths are one way; the wire runs out and back.

Current5 ft10 ft15 ft20 ft30 ft50 ft
5 A18 AWG18 AWG18 AWG16 AWG14 AWG12 AWG
10 A18 AWG16 AWG14 AWG14 AWG12 AWG10 AWG
15 A18 AWG14 AWG14 AWG12 AWG10 AWG8 AWG
20 A16 AWG14 AWG12 AWG10 AWG8 AWG6 AWG
30 A14 AWG12 AWG10 AWG8 AWG8 AWG4 AWG
50 A12 AWG10 AWG8 AWG6 AWG4 AWG3 AWG
100 A10 AWG6 AWG4 AWG4 AWG2 AWG1/0 AWG

Wire gauge for 48 V at 10% drop

10% (4.8 V) is acceptable for non-critical loads such as cabin lighting on boats under ABYC E-11. Avoid it for electronics, pumps and chargers.

Current5 ft10 ft15 ft20 ft30 ft50 ft
5 A18 AWG18 AWG18 AWG18 AWG18 AWG18 AWG
10 A18 AWG18 AWG18 AWG18 AWG18 AWG14 AWG
15 A18 AWG18 AWG18 AWG18 AWG16 AWG14 AWG
20 A18 AWG18 AWG18 AWG16 AWG14 AWG12 AWG
30 A18 AWG18 AWG16 AWG14 AWG12 AWG10 AWG
50 A18 AWG14 AWG14 AWG12 AWG10 AWG8 AWG
100 A14 AWG12 AWG10 AWG8 AWG8 AWG4 AWG

Formula

VD = 2 × R × L × I ÷ 1,000

R is the conductor resistance in ohms per 1,000 ft (NEC Chapter 9, Table 8), L is the one-way length in feet and I is the load current in amps. The 2 counts the wire out and the wire back; on three-phase circuits the return current is shared, so the factor becomes √3, or 1.732.

Charts check voltage drop only. Make sure the wire is also rated for the current: see the battery cable and automotive wire calculators.

Common questions

Do I enter the one-way length or the total wire?

Enter the one-way distance from the panel or source to the load. The calculator doubles it for the out-and-back path on single-phase and DC circuits, and applies the 1.732 factor for three-phase.

What voltage drop is acceptable at 48 V?

3% is the common target for anything that matters: electronics, fridges, pumps and chargers. At 48 V that is 1.44 V. Lighting can tolerate up to 10%.

Should I count the ground return through the chassis?

If the negative returns through a vehicle frame, count only the positive wire length, but the frame connection itself adds resistance. A dedicated negative wire, sized the same as the positive, is more predictable.

Sources

  • NFPA 70, National Electrical Code, 2023 edition (https://www.nfpa.org/codes-and-standards/nfpa-70-standard-development/70)
  • ABYC E-11, AC and DC Electrical Systems on Boats (https://abycinc.org/)