Battery cable size calculator
Battery cables have to carry the current without overheating and without losing too much voltage. Enter the current, system voltage and cable length.
Cable size
Fill in the circuit, then press the button.
Battery cable by amps and length, 12 V, 3%
| Current | 2 ft | 4 ft | 6 ft | 8 ft | 10 ft | 15 ft |
|---|---|---|---|---|---|---|
| 50 A | 10 AWG | 8 AWG | 6 AWG | 4 AWG | 4 AWG | 2 AWG |
| 100 A | 8 AWG | 4 AWG | 3 AWG | 2 AWG | 1 AWG | 2/0 AWG |
| 150 A | 6 AWG | 3 AWG | 2 AWG | 1/0 AWG | 2/0 AWG | 3/0 AWG |
| 200 A | 4 AWG | 2 AWG | 1/0 AWG | 2/0 AWG | 3/0 AWG | 250 kcmil |
| 250 A | 4 AWG | 1 AWG | 2/0 AWG | 3/0 AWG | 4/0 AWG | 300 kcmil |
| 300 A | 3 AWG | 1/0 AWG | 2/0 AWG | 4/0 AWG | 250 kcmil | 350 kcmil |
Voltage drop only. Check the result against the 90 °C ampacity below; the larger of the two wins.
Ampacity of welding and battery cable sizes
| Size | 90 °C ampacity (310.16) |
|---|---|
| 8 AWG | 55 A |
| 6 AWG | 75 A |
| 4 AWG | 95 A |
| 2 AWG | 130 A |
| 1 AWG | 145 A |
| 1/0 AWG | 170 A |
| 2/0 AWG | 195 A |
| 3/0 AWG | 225 A |
| 4/0 AWG | 260 A |
Fine-stranded welding and battery cables often carry higher manufacturer ratings in free air; use those only if the cable is listed for it.
Common questions
What size battery cable for 200 amps?
At 90 °C, 3/0 copper (225 A) for ampacity; at 12 V over 6 ft, voltage drop allows 1/0 AWG. Use 3/0.
Related calculators
Sources
- NFPA 70, National Electrical Code, 2023 edition (https://www.nfpa.org/codes-and-standards/nfpa-70-standard-development/70)
- ABYC E-11, AC and DC Electrical Systems on Boats (https://abycinc.org/)