Voltage Drop Calculator

HomeDC & solar

Inverter cable size calculator

Inverters pull large DC currents, so the battery cables carry far more amps than the AC side. Enter the inverter's continuous rating and the cable length.

W
One way, battery to inverter. Keep it as short as you can.
85% is a fair figure for full load; check the spec sheet.
%
%

Battery cable

Fill in the circuit, then press the button.

Current by inverter size

Inverter12 V24 V48 V
500 W49 A25 A12 A
1,000 W98 A49 A25 A
1,500 W147 A74 A37 A
2,000 W196 A98 A49 A
3,000 W294 A147 A74 A
4,000 W392 A196 A98 A
5,000 W490 A245 A123 A
6,000 W588 A294 A147 A

At full load, 85% efficiency, nominal battery voltage.

Inverter pages

Put a fuse or breaker rated for DC within 7 in of the battery positive, or as close as practical. Class T fuses are common for inverters because of their high interrupting rating.

Common questions

Why is the inverter cable so big?

A 2,000 W inverter on 12 V draws about 200 A. The same power at 120 V AC is under 17 A. Current, not watts, sets the cable size.

Sources

  • NFPA 70, National Electrical Code, 2023 edition (https://www.nfpa.org/codes-and-standards/nfpa-70-standard-development/70)
  • ABYC E-11, AC and DC Electrical Systems on Boats (https://abycinc.org/)