Voltage Drop Calculator

HomeDC & solar

Charge controller to battery wire size

The controller's output is its rated charging current, often 20 to 100 A at battery voltage. Keep this run short and the drop under 2% so the controller reads battery voltage accurately.

V
A
One way. The wire runs out and back.
%

Wire size

Fill in the circuit, then press the button.

Controller output wire, 2% drop

Controller12 V, 5 ft24 V, 5 ft48 V, 10 ft
20 A10 AWG12 AWG12 AWG
30 A8 AWG10 AWG10 AWG
40 A8 AWG8 AWG8 AWG
60 A6 AWG6 AWG6 AWG
80 A4 AWG4 AWG4 AWG
100 A3 AWG3 AWG3 AWG

Copper, 90 °C ampacity at 125% of the controller rating.

Protection

Put a DC-rated fuse or breaker between the controller and the battery, sized at about 125% of the controller's output rating unless the manual says otherwise.

Common questions

What size wire for a 40 A charge controller?

At 12 V and 5 ft, 8 AWG copper.

Sources

  • NFPA 70, National Electrical Code, 2023 edition (https://www.nfpa.org/codes-and-standards/nfpa-70-standard-development/70)