Voltage Drop Calculator

HomeDC & solar

Solar panel wire size calculator

PV conductors are sized at 156% of the panels' short-circuit current: 125% for sunlight above standard test conditions, and another 125% for the continuous load. Then check voltage drop.

A
A
V
One way, from the source to the load.
Most installers aim for 2% or less on PV source circuits.
%

PV wire

Fill in the circuit, then press the button.

The 156% rule

Ampacity ≥ Isc × parallel strings × 1.25 × 1.25

NEC 690.8(A) sets the maximum circuit current at 125% of Isc, and 690.8(B) requires the conductor to carry 125% of that. Series panels add voltage, not current, so long strings are cheap to wire.

Common PV source circuits

IscStringsRequired ampacityCopper (90 °C)
6 A19.4 A14 AWG
10 A115.6 A14 AWG
11.5 A118.0 A14 AWG
14 A121.9 A14 AWG
10 A231.2 A10 AWG
14 A243.8 A8 AWG
10 A346.9 A8 AWG

Before temperature correction. Rooftop conduit and attic runs need the ambient correction factor too.

Common questions

What size wire for solar panels?

Single strings of residential panels (Isc under 14 A) are commonly run on 10 AWG PV wire, rated 40 A at 90 °C. Two or more strings combined need larger conductors.

Sources

  • NFPA 70, National Electrical Code, 2023 edition (https://www.nfpa.org/codes-and-standards/nfpa-70-standard-development/70)
  • https://www.nrel.gov/pv/