Voltage Drop Calculator

HomeVoltage drop

208 volt voltage drop calculator

208 V is the line-to-line voltage of a 120/208 V three-phase system, common in apartments and commercial buildings. Single-phase 208 V loads such as ranges and water heaters see a smaller margin than on 240 V. Enter your wire size, load and distance.

V
A
One way, from the source to the load.
3% for a branch circuit or feeder is the NEC informational guideline.
%

Voltage drop

Fill in the circuit, then press the button.

Volts allowed at 208 V

Target1%2%3%5%
Volts lost2.1 V4.2 V6.2 V10.4 V

At 208 V, the NEC's 3% suggestion means losing no more than 6.2 V between the panel and the load, leaving 201.8 V at the equipment.

Maximum one-way distance at 3%, 208 V single-phase

Load12 AWG10 AWG8 AWG6 AWG4 AWG
20 A78 ft125 ft200 ft317 ft506 ft
30 A—83 ft133 ft211 ft337 ft
40 A——100 ft158 ft253 ft
50 A——80 ft127 ft202 ft

Copper, 75 °C ampacity. A dash means the wire is too small for that current. For aluminum, multiply each distance by about 0.61.

Drop on 10 AWG at 24 A

One-way lengthDropDrop %At the load
25 ft1.49 V0.72%206.5 V
50 ft2.98 V1.43%205.0 V
100 ft5.95 V2.86%202.0 V
150 ft8.93 V4.29%199.1 V
200 ft11.90 V5.72%196.1 V
300 ft17.86 V8.58%190.1 V

R is the conductor resistance in ohms per 1,000 ft (NEC Chapter 9, Table 8), L is the one-way length in feet and I is the load current in amps. The 2 counts the wire out and the wire back; on three-phase circuits the return current is shared, so the factor becomes √3, or 1.732.

Common questions

Do I enter the one-way length or the total wire?

Enter the one-way distance from the panel or source to the load. The calculator doubles it for the out-and-back path on single-phase and DC circuits, and applies the 1.732 factor for three-phase.

Is 3% voltage drop a code requirement?

Not in most cases. The NEC puts the 3% branch-circuit and 5% total figures in informational notes, which explain good practice but are not enforceable on their own. A few sections do set hard limits, such as 647.4(D) for sensitive electronic equipment and 695.7 for fire pumps, and some energy codes and job specifications make 3% or 5% mandatory.

How far can I run 10 AWG at 208 V?

At 20 A, 10 AWG copper reaches about 125 ft one way before the drop passes 3%. Double the current and the distance halves.

Sources

  • NFPA 70, National Electrical Code, 2023 edition (https://www.nfpa.org/codes-and-standards/nfpa-70-standard-development/70)
  • https://www.southwire.com/calculator-vdrop