208 volt voltage drop calculator
208 V is the line-to-line voltage of a 120/208 V three-phase system, common in apartments and commercial buildings. Single-phase 208 V loads such as ranges and water heaters see a smaller margin than on 240 V. Enter your wire size, load and distance.
Voltage drop
Fill in the circuit, then press the button.
Volts allowed at 208 V
| Target | 1% | 2% | 3% | 5% |
|---|---|---|---|---|
| Volts lost | 2.1 V | 4.2 V | 6.2 V | 10.4 V |
At 208 V, the NEC's 3% suggestion means losing no more than 6.2 V between the panel and the load, leaving 201.8 V at the equipment.
Maximum one-way distance at 3%, 208 V single-phase
| Load | 12 AWG | 10 AWG | 8 AWG | 6 AWG | 4 AWG |
|---|---|---|---|---|---|
| 20 A | 78 ft | 125 ft | 200 ft | 317 ft | 506 ft |
| 30 A | — | 83 ft | 133 ft | 211 ft | 337 ft |
| 40 A | — | — | 100 ft | 158 ft | 253 ft |
| 50 A | — | — | 80 ft | 127 ft | 202 ft |
Copper, 75 °C ampacity. A dash means the wire is too small for that current. For aluminum, multiply each distance by about 0.61.
Drop on 10 AWG at 24 A
| One-way length | Drop | Drop % | At the load |
|---|---|---|---|
| 25 ft | 1.49 V | 0.72% | 206.5 V |
| 50 ft | 2.98 V | 1.43% | 205.0 V |
| 100 ft | 5.95 V | 2.86% | 202.0 V |
| 150 ft | 8.93 V | 4.29% | 199.1 V |
| 200 ft | 11.90 V | 5.72% | 196.1 V |
| 300 ft | 17.86 V | 8.58% | 190.1 V |
R is the conductor resistance in ohms per 1,000 ft (NEC Chapter 9, Table 8), L is the one-way length in feet and I is the load current in amps. The 2 counts the wire out and the wire back; on three-phase circuits the return current is shared, so the factor becomes √3, or 1.732.
Common questions
Do I enter the one-way length or the total wire?
Enter the one-way distance from the panel or source to the load. The calculator doubles it for the out-and-back path on single-phase and DC circuits, and applies the 1.732 factor for three-phase.
Is 3% voltage drop a code requirement?
Not in most cases. The NEC puts the 3% branch-circuit and 5% total figures in informational notes, which explain good practice but are not enforceable on their own. A few sections do set hard limits, such as 647.4(D) for sensitive electronic equipment and 695.7 for fire pumps, and some energy codes and job specifications make 3% or 5% mandatory.
How far can I run 10 AWG at 208 V?
At 20 A, 10 AWG copper reaches about 125 ft one way before the drop passes 3%. Double the current and the distance halves.