Dim, color-shifted ends on LED tape come from voltage drop, both in the strip and in the wire from the driver. Enter the feed wire and the strip's current draw.

V
A
One way, from the source to the load.
3% for a branch circuit or feeder is the NEC informational guideline.
%

Feed wire drop

Fill in the circuit, then press the button.

Find the strip current

I = watts per foot × feet ÷ volts

StripPer 16.4 ft reel at 12 VPer reel at 24 V
1.2 W/ft1.6 A0.8 A
2.2 W/ft3.0 A1.5 A
4.4 W/ft6.0 A3.0 A
6 W/ft8.2 A4.1 A

Feed wire gauge for 12 V strips, 5% drop

Current5 ft10 ft15 ft25 ft40 ft
2 A18 AWG18 AWG18 AWG16 AWG14 AWG
4 A18 AWG16 AWG16 AWG12 AWG10 AWG
6 A18 AWG16 AWG14 AWG12 AWG10 AWG
8 A16 AWG14 AWG12 AWG10 AWG8 AWG
10 A16 AWG12 AWG12 AWG8 AWG6 AWG
15 A14 AWG12 AWG10 AWG8 AWG6 AWG

Strip makers commonly suggest feeding from both ends or every 16 ft on 12 V tape, and every 32 ft on 24 V, because the strip's own copper traces drop voltage too.

24 V strips, 5% drop

Current5 ft10 ft15 ft25 ft40 ft60 ft
2 A18 AWG18 AWG18 AWG18 AWG16 AWG16 AWG
4 A18 AWG18 AWG18 AWG16 AWG14 AWG12 AWG
6 A18 AWG18 AWG16 AWG14 AWG12 AWG10 AWG
8 A18 AWG16 AWG16 AWG12 AWG10 AWG10 AWG
10 A18 AWG16 AWG14 AWG12 AWG10 AWG8 AWG
15 A18 AWG14 AWG12 AWG10 AWG8 AWG6 AWG

Common questions

Why does the end of my LED strip look dimmer?

The thin copper traces in the strip drop voltage along its length. Feed long runs from both ends, inject power in the middle, or switch to 24 V tape.

Do I enter the one-way length or the total wire?

Enter the one-way distance from the panel or source to the load. The calculator doubles it for the out-and-back path on single-phase and DC circuits, and applies the 1.732 factor for three-phase.

Sources

  • NFPA 70, National Electrical Code, 2023 edition (https://www.nfpa.org/codes-and-standards/nfpa-70-standard-development/70)