Voltage drop calculator for mm² cable

For cables sized in square millimeters. Resistance is from IEC 60228, corrected to a 70 °C operating temperature.

V
A
m
%

Voltage drop

Fill in the circuit, then press the button.

Resistance of metric conductors

CableCopper Ω/km (20 °C)Copper Ω/km (70 °C)Aluminium Ω/km (20 °C)
1.5 mm²12.114.478—
2.5 mm²7.418.866—
4 mm²4.615.516—
6 mm²3.083.685—
10 mm²1.832.190—
16 mm²1.151.3761.91
25 mm²0.7270.8701.2
35 mm²0.5240.6270.868
50 mm²0.3870.4630.641
70 mm²0.2680.3210.443
95 mm²0.1930.2310.32
120 mm²0.1530.1830.253
150 mm²0.1240.1480.206
185 mm²0.09910.1190.164
240 mm²0.07540.0900.125
300 mm²0.06010.0720.1

Maximum DC resistance, IEC 60228 class 2 stranded conductors.

AWG to mm² equivalents

AWGmm²Nearest metric size
14 AWG2.082.5 mm² (larger)
12 AWG3.314 mm²
10 AWG5.266 mm²
8 AWG8.3710 mm²
6 AWG13.3016 mm²
4 AWG21.1525 mm²
2 AWG33.6235 mm²
1/0 AWG53.5150 mm²
2/0 AWG67.4470 mm²
4/0 AWG107.22120 mm²

Common questions

Which voltage drop limit applies with metric cable?

It depends on the country. The UK uses 3% for lighting and 5% for other circuits, Australia and New Zealand 5% from the point of supply, and IEC 60364-5-52 suggests 3% for lighting and 5% for other uses on public supplies.

Sources

  • IEC 60228:2004, Conductors of insulated cables (International Electrotechnical Commission)
  • BS 7671:2018+A2:2022, Appendix 4 (https://electrical.theiet.org/bs-7671/)
  • AS/NZS 3000:2018 Electrical installations (Wiring Rules), clause 3.6.2