Voltage drop calculator for mm² cable
For cables sized in square millimeters. Resistance is from IEC 60228, corrected to a 70 °C operating temperature.
Voltage drop
Fill in the circuit, then press the button.
Resistance of metric conductors
| Cable | Copper Ω/km (20 °C) | Copper Ω/km (70 °C) | Aluminium Ω/km (20 °C) |
|---|---|---|---|
| 1.5 mm² | 12.1 | 14.478 | — |
| 2.5 mm² | 7.41 | 8.866 | — |
| 4 mm² | 4.61 | 5.516 | — |
| 6 mm² | 3.08 | 3.685 | — |
| 10 mm² | 1.83 | 2.190 | — |
| 16 mm² | 1.15 | 1.376 | 1.91 |
| 25 mm² | 0.727 | 0.870 | 1.2 |
| 35 mm² | 0.524 | 0.627 | 0.868 |
| 50 mm² | 0.387 | 0.463 | 0.641 |
| 70 mm² | 0.268 | 0.321 | 0.443 |
| 95 mm² | 0.193 | 0.231 | 0.32 |
| 120 mm² | 0.153 | 0.183 | 0.253 |
| 150 mm² | 0.124 | 0.148 | 0.206 |
| 185 mm² | 0.0991 | 0.119 | 0.164 |
| 240 mm² | 0.0754 | 0.090 | 0.125 |
| 300 mm² | 0.0601 | 0.072 | 0.1 |
Maximum DC resistance, IEC 60228 class 2 stranded conductors.
AWG to mm² equivalents
| AWG | mm² | Nearest metric size |
|---|---|---|
| 14 AWG | 2.08 | 2.5 mm² (larger) |
| 12 AWG | 3.31 | 4 mm² |
| 10 AWG | 5.26 | 6 mm² |
| 8 AWG | 8.37 | 10 mm² |
| 6 AWG | 13.30 | 16 mm² |
| 4 AWG | 21.15 | 25 mm² |
| 2 AWG | 33.62 | 35 mm² |
| 1/0 AWG | 53.51 | 50 mm² |
| 2/0 AWG | 67.44 | 70 mm² |
| 4/0 AWG | 107.22 | 120 mm² |
Common questions
Which voltage drop limit applies with metric cable?
It depends on the country. The UK uses 3% for lighting and 5% for other circuits, Australia and New Zealand 5% from the point of supply, and IEC 60364-5-52 suggests 3% for lighting and 5% for other uses on public supplies.
Related calculators
Sources
- IEC 60228:2004, Conductors of insulated cables (International Electrotechnical Commission)
- BS 7671:2018+A2:2022, Appendix 4 (https://electrical.theiet.org/bs-7671/)
- AS/NZS 3000:2018 Electrical installations (Wiring Rules), clause 3.6.2