Voltage Drop Calculator

HomeOutside the U.S.

Australian voltage drop calculator

AS/NZS 3000 limits voltage drop to 5% from the point of supply to any point in the installation. That 5% covers the consumer mains, submains and final circuit together.

V
A
m
%

Voltage drop

Fill in the circuit, then press the button.

The 5% budget

Supply5% total
230 V single-phase11.5 V
400 V three-phase20 V

A common split is 1 to 2% for consumer mains, the rest across submains and final subcircuits. AS/NZS 3008.1.1 gives the Vc values used for formal calculations; this tool uses IEC 60228 resistance at 70 °C, which lands close for cables up to about 35 mm².

Typical final subcircuits

CircuitCableMax length at 5% alone
Lighting 10 A1.5 mm²40 m
Power 20 A2.5 mm²32 m
Power 20 A4 mm²52 m
Cooktop 32 A6 mm²49 m
Air conditioner 25 A4 mm²42 m

Whole 5% used by the final circuit; leave room for mains and submains.

Common questions

Is the 5% voltage drop rule mandatory in Australia?

Yes. Clause 3.6.2 of AS/NZS 3000 sets it.

Sources

  • AS/NZS 3000:2018 Electrical installations (Wiring Rules), clause 3.6.2
  • AS/NZS 3008.1.1:2017 Electrical installations, selection of cables