Australian voltage drop calculator
AS/NZS 3000 limits voltage drop to 5% from the point of supply to any point in the installation. That 5% covers the consumer mains, submains and final circuit together.
Voltage drop
Fill in the circuit, then press the button.
The 5% budget
| Supply | 5% total |
|---|---|
| 230 V single-phase | 11.5 V |
| 400 V three-phase | 20 V |
A common split is 1 to 2% for consumer mains, the rest across submains and final subcircuits. AS/NZS 3008.1.1 gives the Vc values used for formal calculations; this tool uses IEC 60228 resistance at 70 °C, which lands close for cables up to about 35 mm².
Typical final subcircuits
| Circuit | Cable | Max length at 5% alone |
|---|---|---|
| Lighting 10 A | 1.5 mm² | 40 m |
| Power 20 A | 2.5 mm² | 32 m |
| Power 20 A | 4 mm² | 52 m |
| Cooktop 32 A | 6 mm² | 49 m |
| Air conditioner 25 A | 4 mm² | 42 m |
Whole 5% used by the final circuit; leave room for mains and submains.
Common questions
Is the 5% voltage drop rule mandatory in Australia?
Yes. Clause 3.6.2 of AS/NZS 3000 sets it.
Related calculators
Sources
- AS/NZS 3000:2018 Electrical installations (Wiring Rules), clause 3.6.2
- AS/NZS 3008.1.1:2017 Electrical installations, selection of cables
- IEC 60228:2004, Conductors of insulated cables (International Electrotechnical Commission)