Canada voltage drop calculator
The Canadian Electrical Code makes voltage drop mandatory: 5% from the supply side of the consumer's service to the point of use, and 3% in any feeder or branch circuit.
Voltage drop
Fill in the circuit, then press the button.
CEC Rule 8-102
| Portion | Limit | 120 V | 240 V | 600 V |
|---|---|---|---|---|
| Feeder or branch circuit | 3% | 3.6 V | 7.2 V | 18 V |
| Service to point of use | 5% | 6 V | 12 V | 30 V |
Rule 8-102 is based on the demand load or 80% of the overcurrent device rating, depending on the case. Table D3 in the CEC gives distance multipliers that reach the same result as this calculator.
600 V three-phase
Many Canadian commercial buildings use 347/600 V. Set the calculator to three-phase, 600 V, for those feeders.
Common questions
Is voltage drop mandatory in Canada?
Yes. Unlike the NEC's informational notes, CEC Rule 8-102 is an enforceable requirement.