Voltage Drop Calculator

HomeOutside the U.S.

Three-phase SWA voltage drop

For 400 V three-phase supplies and SWA submains to outbuildings. Enter the phase current and length.

V
A
m
%

Voltage drop

Fill in the circuit, then press the button.

400 V limits

Circuit3%5%
400 V three-phase12 V20 V
230 V single-phase6.9 V11.5 V

SWA to an outbuilding

A single-phase submain to a garden office is usually 3-core SWA. Figure it as single-phase at 230 V; use the 3-phase setting only for a true three-phase supply. Remember the submain's drop adds to the final circuits at the far end.

Common questions

What size SWA for 100 m at 32 A?

At 230 V single-phase and 5% overall, 10 mm² gives about 14 V, over the limit; 16 mm² gives about 9 V.

Sources

  • BS 7671:2018+A2:2022, Appendix 4 (https://electrical.theiet.org/bs-7671/)