Three-phase SWA voltage drop
For 400 V three-phase supplies and SWA submains to outbuildings. Enter the phase current and length.
Voltage drop
Fill in the circuit, then press the button.
400 V limits
| Circuit | 3% | 5% |
|---|---|---|
| 400 V three-phase | 12 V | 20 V |
| 230 V single-phase | 6.9 V | 11.5 V |
SWA to an outbuilding
A single-phase submain to a garden office is usually 3-core SWA. Figure it as single-phase at 230 V; use the 3-phase setting only for a true three-phase supply. Remember the submain's drop adds to the final circuits at the far end.
Common questions
What size SWA for 100 m at 32 A?
At 230 V single-phase and 5% overall, 10 mm² gives about 14 V, over the limit; 16 mm² gives about 9 V.