Voltage Drop Calculator

HomeOutside the U.S.

New Zealand voltage drop calculator

New Zealand uses AS/NZS 3000, the same Wiring Rules as Australia: 5% maximum from the point of supply.

V
A
m
%

Voltage drop

Fill in the circuit, then press the button.

Cable resistance used

CableCu Ω/km at 70 °CAl Ω/km at 70 °C
1.5 mm²14.478—
2.5 mm²8.866—
4 mm²5.516—
6 mm²3.685—
10 mm²2.190—
16 mm²1.3762.285
25 mm²0.8701.436
35 mm²0.6271.039
50 mm²0.4630.767
70 mm²0.3210.530
95 mm²0.2310.383
120 mm²0.1830.303
150 mm²0.1480.246
185 mm²0.1190.196
240 mm²0.0900.150
300 mm²0.0720.120

Rural supplies

Long rural service mains, such as a run from a roadside transformer to a farmhouse, often consume most of the 5% before the switchboard. Calculate the mains first, then size final circuits with what is left.

Common questions

Does NZ use the same rules as Australia?

For voltage drop, yes: AS/NZS 3000 is a joint standard, and NZ cites it through the Electricity (Safety) Regulations.

Sources

  • AS/NZS 3000:2018 Electrical installations (Wiring Rules), clause 3.6.2
  • IEC 60228:2004, Conductors of insulated cables (International Electrotechnical Commission)