New Zealand voltage drop calculator
New Zealand uses AS/NZS 3000, the same Wiring Rules as Australia: 5% maximum from the point of supply.
Voltage drop
Fill in the circuit, then press the button.
Cable resistance used
| Cable | Cu Ω/km at 70 °C | Al Ω/km at 70 °C |
|---|---|---|
| 1.5 mm² | 14.478 | — |
| 2.5 mm² | 8.866 | — |
| 4 mm² | 5.516 | — |
| 6 mm² | 3.685 | — |
| 10 mm² | 2.190 | — |
| 16 mm² | 1.376 | 2.285 |
| 25 mm² | 0.870 | 1.436 |
| 35 mm² | 0.627 | 1.039 |
| 50 mm² | 0.463 | 0.767 |
| 70 mm² | 0.321 | 0.530 |
| 95 mm² | 0.231 | 0.383 |
| 120 mm² | 0.183 | 0.303 |
| 150 mm² | 0.148 | 0.246 |
| 185 mm² | 0.119 | 0.196 |
| 240 mm² | 0.090 | 0.150 |
| 300 mm² | 0.072 | 0.120 |
Rural supplies
Long rural service mains, such as a run from a roadside transformer to a farmhouse, often consume most of the 5% before the switchboard. Calculate the mains first, then size final circuits with what is left.
Common questions
Does NZ use the same rules as Australia?
For voltage drop, yes: AS/NZS 3000 is a joint standard, and NZ cites it through the Electricity (Safety) Regulations.
Related calculators
Sources
- AS/NZS 3000:2018 Electrical installations (Wiring Rules), clause 3.6.2
- IEC 60228:2004, Conductors of insulated cables (International Electrotechnical Commission)