UK voltage drop calculator
BS 7671 gives voltage drop as millivolts per amp per metre. Enter the design current, cable length and size.
Voltage drop
Fill in the circuit, then press the button.
BS 7671 limits
| Circuit | Limit | At 230 V |
|---|---|---|
| Lighting | 3% | 6.9 V |
| Other uses | 5% | 11.5 V |
Appendix 4, Table 4Ab, for installations supplied directly from a public low-voltage network.
mV/A/m values
| Cable | mV/A/m | Max length at 20 A, 5% |
|---|---|---|
| 1 mm² | 44 | 13 m |
| 1.5 mm² | 29 | 20 m |
| 2.5 mm² | 18 | 32 m |
| 4 mm² | 11 | 52 m |
| 6 mm² | 7.3 | 79 m |
| 10 mm² | 4.4 | 131 m |
| 16 mm² | 2.8 | 205 m |
| 25 mm² | 1.75 | 329 m |
| 35 mm² | 1.25 | 460 m |
| 50 mm² | 0.93 | 618 m |
| 70 mm² | 0.63 | 913 m |
| 95 mm² | 0.46 | 1250 m |
| 120 mm² | 0.36 | 1597 m |
| 150 mm² | 0.29 | 1983 m |
Two-core 70 °C thermoplastic copper, single-phase.
Common questions
How far can 2.5 mm² cable run at 20 A?
With 18 mV/A/m, 20 A drops 0.36 V per metre, so 5% (11.5 V) is reached at about 32 m on a radial circuit. Ring circuits share the current both ways and run much farther.
Related calculators
Sources
- BS 7671:2018+A2:2022, Appendix 4 (https://electrical.theiet.org/bs-7671/)