240 volt voltage drop calculator

240 V circuits feed ranges, dryers, water heaters, EV chargers, well pumps and subpanels. At the same wattage they draw half the current of 120 V, so they reach about four times as far on the same wire. Enter your wire size, load and distance.

V
A
One way, from the source to the load.
3% for a branch circuit or feeder is the NEC informational guideline.
%

Voltage drop

Fill in the circuit, then press the button.

Volts allowed at 240 V

Target1%2%3%5%
Volts lost2.4 V4.8 V7.2 V12.0 V

At 240 V, the NEC's 3% suggestion means losing no more than 7.2 V between the panel and the load, leaving 232.8 V at the equipment.

Maximum one-way distance at 3%, 240 V single-phase

Load12 AWG10 AWG8 AWG6 AWG4 AWG
20 A90 ft145 ft231 ft366 ft584 ft
30 A—96 ft154 ft244 ft389 ft
40 A——115 ft183 ft292 ft
50 A——92 ft146 ft233 ft
60 A———122 ft194 ft

Copper, 75 °C ampacity. A dash means the wire is too small for that current. For aluminum, multiply each distance by about 0.61.

Drop on 10 AWG at 24 A

One-way lengthDropDrop %At the load
25 ft1.49 V0.62%238.5 V
50 ft2.98 V1.24%237.0 V
100 ft5.95 V2.48%234.0 V
150 ft8.93 V3.72%231.1 V
200 ft11.90 V4.96%228.1 V
300 ft17.86 V7.44%222.1 V

R is the conductor resistance in ohms per 1,000 ft (NEC Chapter 9, Table 8), L is the one-way length in feet and I is the load current in amps. The 2 counts the wire out and the wire back; on three-phase circuits the return current is shared, so the factor becomes √3, or 1.732.

Common questions

Do I enter the one-way length or the total wire?

Enter the one-way distance from the panel or source to the load. The calculator doubles it for the out-and-back path on single-phase and DC circuits, and applies the 1.732 factor for three-phase.

Is 3% voltage drop a code requirement?

Not in most cases. The NEC puts the 3% branch-circuit and 5% total figures in informational notes, which explain good practice but are not enforceable on their own. A few sections do set hard limits, such as 647.4(D) for sensitive electronic equipment and 695.7 for fire pumps, and some energy codes and job specifications make 3% or 5% mandatory.

How far can I run 10 AWG at 240 V?

At 20 A, 10 AWG copper reaches about 145 ft one way before the drop passes 3%. Double the current and the distance halves.