240 volt voltage drop calculator
240 V circuits feed ranges, dryers, water heaters, EV chargers, well pumps and subpanels. At the same wattage they draw half the current of 120 V, so they reach about four times as far on the same wire. Enter your wire size, load and distance.
Voltage drop
Fill in the circuit, then press the button.
Volts allowed at 240 V
| Target | 1% | 2% | 3% | 5% |
|---|---|---|---|---|
| Volts lost | 2.4 V | 4.8 V | 7.2 V | 12.0 V |
At 240 V, the NEC's 3% suggestion means losing no more than 7.2 V between the panel and the load, leaving 232.8 V at the equipment.
Maximum one-way distance at 3%, 240 V single-phase
| Load | 12 AWG | 10 AWG | 8 AWG | 6 AWG | 4 AWG |
|---|---|---|---|---|---|
| 20 A | 90 ft | 145 ft | 231 ft | 366 ft | 584 ft |
| 30 A | — | 96 ft | 154 ft | 244 ft | 389 ft |
| 40 A | — | — | 115 ft | 183 ft | 292 ft |
| 50 A | — | — | 92 ft | 146 ft | 233 ft |
| 60 A | — | — | — | 122 ft | 194 ft |
Copper, 75 °C ampacity. A dash means the wire is too small for that current. For aluminum, multiply each distance by about 0.61.
Drop on 10 AWG at 24 A
| One-way length | Drop | Drop % | At the load |
|---|---|---|---|
| 25 ft | 1.49 V | 0.62% | 238.5 V |
| 50 ft | 2.98 V | 1.24% | 237.0 V |
| 100 ft | 5.95 V | 2.48% | 234.0 V |
| 150 ft | 8.93 V | 3.72% | 231.1 V |
| 200 ft | 11.90 V | 4.96% | 228.1 V |
| 300 ft | 17.86 V | 7.44% | 222.1 V |
R is the conductor resistance in ohms per 1,000 ft (NEC Chapter 9, Table 8), L is the one-way length in feet and I is the load current in amps. The 2 counts the wire out and the wire back; on three-phase circuits the return current is shared, so the factor becomes √3, or 1.732.
Common questions
Do I enter the one-way length or the total wire?
Enter the one-way distance from the panel or source to the load. The calculator doubles it for the out-and-back path on single-phase and DC circuits, and applies the 1.732 factor for three-phase.
Is 3% voltage drop a code requirement?
Not in most cases. The NEC puts the 3% branch-circuit and 5% total figures in informational notes, which explain good practice but are not enforceable on their own. A few sections do set hard limits, such as 647.4(D) for sensitive electronic equipment and 695.7 for fire pumps, and some energy codes and job specifications make 3% or 5% mandatory.
How far can I run 10 AWG at 240 V?
At 20 A, 10 AWG copper reaches about 145 ft one way before the drop passes 3%. Double the current and the distance halves.
Related calculators
Sources
- NFPA 70, National Electrical Code, 2023 edition (https://www.nfpa.org/codes-and-standards/nfpa-70-standard-development/70)
- https://www.southwire.com/calculator-vdrop