480 volt voltage drop calculator
480 V three-phase feeds motors, HVAC and commercial distribution. Drop is figured with the 1.732 factor because the three phases share the return current. Enter your wire size, load and distance.
Voltage drop
Fill in the circuit, then press the button.
Volts allowed at 480 V
| Target | 1% | 2% | 3% | 5% |
|---|---|---|---|---|
| Volts lost | 4.8 V | 9.6 V | 14.4 V | 24.0 V |
At 480 V, the NEC's 3% suggestion means losing no more than 14.4 V between the panel and the load, leaving 465.6 V at the equipment.
Maximum one-way distance at 3%, 480 V three-phase
| Load | 10 AWG | 8 AWG | 6 AWG | 4 AWG | 2 AWG |
|---|---|---|---|---|---|
| 20 A | 335 ft | 534 ft | 846 ft | 1,349 ft | 2,142 ft |
| 40 A | — | 267 ft | 423 ft | 674 ft | 1,071 ft |
| 60 A | — | — | 282 ft | 449 ft | 714 ft |
| 100 A | — | — | — | — | 428 ft |
Copper, 75 °C ampacity. A dash means the wire is too small for that current. For aluminum, multiply each distance by about 0.61.
Drop on 8 AWG at 40 A
| One-way length | Drop | Drop % | At the load |
|---|---|---|---|
| 25 ft | 1.35 V | 0.28% | 478.7 V |
| 50 ft | 2.70 V | 0.56% | 477.3 V |
| 100 ft | 5.39 V | 1.12% | 474.6 V |
| 150 ft | 8.09 V | 1.68% | 471.9 V |
| 200 ft | 10.78 V | 2.25% | 469.2 V |
| 300 ft | 16.17 V | 3.37% | 463.8 V |
R is the conductor resistance in ohms per 1,000 ft (NEC Chapter 9, Table 8), L is the one-way length in feet and I is the load current in amps. The 2 counts the wire out and the wire back; on three-phase circuits the return current is shared, so the factor becomes √3, or 1.732.
Common questions
Do I enter the one-way length or the total wire?
Enter the one-way distance from the panel or source to the load. The calculator doubles it for the out-and-back path on single-phase and DC circuits, and applies the 1.732 factor for three-phase.
Is 3% voltage drop a code requirement?
Not in most cases. The NEC puts the 3% branch-circuit and 5% total figures in informational notes, which explain good practice but are not enforceable on their own. A few sections do set hard limits, such as 647.4(D) for sensitive electronic equipment and 695.7 for fire pumps, and some energy codes and job specifications make 3% or 5% mandatory.
How far can I run 8 AWG at 480 V?
At 20 A, 8 AWG copper reaches about 534 ft one way before the drop passes 3%. Double the current and the distance halves.
Related calculators
Sources
- NFPA 70, National Electrical Code, 2023 edition (https://www.nfpa.org/codes-and-standards/nfpa-70-standard-development/70)
- https://www.southwire.com/calculator-vdrop