Voltage Drop Calculator

HomeVoltage drop

480 volt voltage drop calculator

480 V three-phase feeds motors, HVAC and commercial distribution. Drop is figured with the 1.732 factor because the three phases share the return current. Enter your wire size, load and distance.

V
A
One way, from the source to the load.
3% for a branch circuit or feeder is the NEC informational guideline.
%

Voltage drop

Fill in the circuit, then press the button.

Volts allowed at 480 V

Target1%2%3%5%
Volts lost4.8 V9.6 V14.4 V24.0 V

At 480 V, the NEC's 3% suggestion means losing no more than 14.4 V between the panel and the load, leaving 465.6 V at the equipment.

Maximum one-way distance at 3%, 480 V three-phase

Load10 AWG8 AWG6 AWG4 AWG2 AWG
20 A335 ft534 ft846 ft1,349 ft2,142 ft
40 A—267 ft423 ft674 ft1,071 ft
60 A——282 ft449 ft714 ft
100 A————428 ft

Copper, 75 °C ampacity. A dash means the wire is too small for that current. For aluminum, multiply each distance by about 0.61.

Drop on 8 AWG at 40 A

One-way lengthDropDrop %At the load
25 ft1.35 V0.28%478.7 V
50 ft2.70 V0.56%477.3 V
100 ft5.39 V1.12%474.6 V
150 ft8.09 V1.68%471.9 V
200 ft10.78 V2.25%469.2 V
300 ft16.17 V3.37%463.8 V

R is the conductor resistance in ohms per 1,000 ft (NEC Chapter 9, Table 8), L is the one-way length in feet and I is the load current in amps. The 2 counts the wire out and the wire back; on three-phase circuits the return current is shared, so the factor becomes √3, or 1.732.

Common questions

Do I enter the one-way length or the total wire?

Enter the one-way distance from the panel or source to the load. The calculator doubles it for the out-and-back path on single-phase and DC circuits, and applies the 1.732 factor for three-phase.

Is 3% voltage drop a code requirement?

Not in most cases. The NEC puts the 3% branch-circuit and 5% total figures in informational notes, which explain good practice but are not enforceable on their own. A few sections do set hard limits, such as 647.4(D) for sensitive electronic equipment and 695.7 for fire pumps, and some energy codes and job specifications make 3% or 5% mandatory.

How far can I run 8 AWG at 480 V?

At 20 A, 8 AWG copper reaches about 534 ft one way before the drop passes 3%. Double the current and the distance halves.