36 volt DC voltage drop calculator
36 V DC powers larger trolling motors, some golf carts and floor machines, usually from three 12 V batteries in series. Cable between the batteries counts toward the drop too. Enter the wire gauge, current and one-way length.
Voltage drop
Fill in the circuit, then press the button.
Wire gauge for 36 V at 3% drop
Smallest copper size that holds the drop to 3% (1.08 V). Lengths are one way; the wire runs out and back.
| Current | 5 ft | 10 ft | 15 ft | 20 ft | 30 ft | 50 ft |
|---|---|---|---|---|---|---|
| 5 A | 18 AWG | 18 AWG | 16 AWG | 16 AWG | 14 AWG | 12 AWG |
| 10 A | 18 AWG | 16 AWG | 14 AWG | 12 AWG | 10 AWG | 8 AWG |
| 15 A | 16 AWG | 14 AWG | 12 AWG | 10 AWG | 8 AWG | 6 AWG |
| 20 A | 16 AWG | 12 AWG | 10 AWG | 10 AWG | 8 AWG | 6 AWG |
| 30 A | 14 AWG | 10 AWG | 8 AWG | 8 AWG | 6 AWG | 4 AWG |
| 50 A | 12 AWG | 8 AWG | 6 AWG | 6 AWG | 4 AWG | 2 AWG |
| 100 A | 8 AWG | 6 AWG | 4 AWG | 3 AWG | 1 AWG | 2/0 AWG |
Wire gauge for 36 V at 10% drop
10% (3.6 V) is acceptable for non-critical loads such as cabin lighting on boats under ABYC E-11. Avoid it for electronics, pumps and chargers.
| Current | 5 ft | 10 ft | 15 ft | 20 ft | 30 ft | 50 ft |
|---|---|---|---|---|---|---|
| 5 A | 18 AWG | 18 AWG | 18 AWG | 18 AWG | 18 AWG | 16 AWG |
| 10 A | 18 AWG | 18 AWG | 18 AWG | 18 AWG | 16 AWG | 14 AWG |
| 15 A | 18 AWG | 18 AWG | 18 AWG | 16 AWG | 14 AWG | 12 AWG |
| 20 A | 18 AWG | 18 AWG | 16 AWG | 14 AWG | 12 AWG | 10 AWG |
| 30 A | 18 AWG | 16 AWG | 14 AWG | 12 AWG | 12 AWG | 8 AWG |
| 50 A | 16 AWG | 14 AWG | 12 AWG | 10 AWG | 8 AWG | 6 AWG |
| 100 A | 14 AWG | 10 AWG | 8 AWG | 8 AWG | 6 AWG | 4 AWG |
Formula
VD = 2 × R × L × I ÷ 1,000
R is the conductor resistance in ohms per 1,000 ft (NEC Chapter 9, Table 8), L is the one-way length in feet and I is the load current in amps. The 2 counts the wire out and the wire back; on three-phase circuits the return current is shared, so the factor becomes √3, or 1.732.
Charts check voltage drop only. Make sure the wire is also rated for the current: see the battery cable and automotive wire calculators.
Common questions
Do I enter the one-way length or the total wire?
Enter the one-way distance from the panel or source to the load. The calculator doubles it for the out-and-back path on single-phase and DC circuits, and applies the 1.732 factor for three-phase.
What voltage drop is acceptable at 36 V?
3% is the common target for anything that matters: electronics, fridges, pumps and chargers. At 36 V that is 1.08 V. Lighting can tolerate up to 10%.
Should I count the ground return through the chassis?
If the negative returns through a vehicle frame, count only the positive wire length, but the frame connection itself adds resistance. A dedicated negative wire, sized the same as the positive, is more predictable.
Related calculators
Sources
- NFPA 70, National Electrical Code, 2023 edition (https://www.nfpa.org/codes-and-standards/nfpa-70-standard-development/70)
- ABYC E-11, AC and DC Electrical Systems on Boats (https://abycinc.org/)