Voltage Drop Formula:
From: | To: |
Definition: This calculator estimates the voltage drop in electrical circuits according to Australian standards using the IPD (Impedance, Power, Distance) method.
Purpose: It helps electricians and engineers ensure proper voltage levels in electrical installations as required by AS/NZS 3000 wiring rules.
The calculator uses the formula:
Where:
Explanation: The formula calculates the voltage drop in a single-phase circuit, accounting for both the outgoing and return paths (hence the factor of 2).
Details: Proper voltage drop calculation ensures electrical equipment receives adequate voltage to operate correctly and prevents excessive power loss in cables.
Tips: Enter the conductor resistivity (default 1.72×10⁻⁸ ohm-m for copper), cable length in meters, current in amps, and conductor cross-sectional area in m². All values must be > 0.
Q1: What's the maximum allowable voltage drop in Australia?
A: AS/NZS 3000 specifies maximum voltage drops of 5% for general circuits and 3% for lighting circuits at the farthest point.
Q2: What resistivity value should I use?
A: For copper at 20°C use 1.72×10⁻⁸ ohm-m. For aluminum use 2.82×10⁻⁸ ohm-m. Adjust for temperature if needed.
Q3: How do I convert mm² to m² for conductor area?
A: Divide mm² by 1,000,000 (e.g., 2.5mm² = 2.5×10⁻⁶ m²).
Q4: Does this work for three-phase systems?
A: This formula is for single-phase. Three-phase calculations use a different formula (VD = √3 × ρ × L × I / A).
Q5: Where can I find standard conductor sizes?
A: Refer to AS/NZS 3008.1.1 for standard Australian cable sizes and their properties.