16 AWG wire

16 AWG is too small for building branch circuits. It is used for speaker wire, landscape lighting leads, extension cords and LED strips. On low-voltage DC runs, voltage drop limits it long before heat does.

V
A
One way, from the source to the load.
3% for a branch circuit or feeder is the NEC informational guideline.
%

Voltage drop

Fill in the circuit, then press the button.

16 AWG specifications

PropertyValue
Diameter, solid0.0508 in (1.29 mm)
Area2,580 cmil (1.307 mm²)
Resistance4.99 Ω per 1,000 ft at 75 °C
Fixture wire ampacity8 A (NEC Table 402.5)

Maximum one-way distance, 3% drop

Current12 V24 V
0.5 A72 ft144 ft
1 A36 ft72 ft
2 A18 ft36 ft
3 A12 ft24 ft
5 A7 ft14 ft

Class 2 power supplies limit the current so that these small wires stay safe; voltage drop is the main design check.

Common questions

How many amps can 16 gauge wire carry?

As fixture wire, 8 A under NEC Table 402.5. Cords and appliance leads have their own ratings in Article 400.

Sources

  • NFPA 70, National Electrical Code, 2023 edition (https://www.nfpa.org/codes-and-standards/nfpa-70-standard-development/70)