AWG wire gauge chart
Pick a size to see every number for it, or scan the full chart below. Each AWG step is about 26% more area; every six gauges doubles the diameter.
Wire data
Fill in the circuit, then press the button.
Full chart
| Size | Diameter | mm² | Cu Ω/kft | Cu amps 60/75/90 °C |
|---|---|---|---|---|
| 18 AWG | 0.0402 in | 0.82 | 7.95 | — |
| 16 AWG | 0.0508 in | 1.31 | 4.99 | — |
| 14 AWG | 0.0641 in | 2.08 | 3.14 | 15/20/25 |
| 12 AWG | 0.0808 in | 3.31 | 1.98 | 20/25/30 |
| 10 AWG | 0.1019 in | 5.26 | 1.24 | 30/35/40 |
| 8 AWG | 0.1285 in | 8.37 | 0.778 | 40/50/55 |
| 6 AWG | 0.1620 in | 13.30 | 0.491 | 55/65/75 |
| 4 AWG | 0.2043 in | 21.15 | 0.308 | 70/85/95 |
| 3 AWG | 0.2294 in | 26.66 | 0.245 | 85/100/115 |
| 2 AWG | 0.2576 in | 33.62 | 0.194 | 95/115/130 |
| 1 AWG | 0.2893 in | 42.41 | 0.154 | 110/130/145 |
| 1/0 AWG | 0.3250 in | 53.51 | 0.122 | 125/150/170 |
| 2/0 AWG | 0.3648 in | 67.44 | 0.0967 | 145/175/195 |
| 3/0 AWG | 0.4096 in | 85.02 | 0.0766 | 165/200/225 |
| 4/0 AWG | 0.4600 in | 107.22 | 0.0608 | 195/230/260 |
| 250 kcmil | 0.5000 in | 126.67 | 0.0515 | 215/255/290 |
| 300 kcmil | 0.5477 in | 152.01 | 0.0429 | 240/285/320 |
| 350 kcmil | 0.5916 in | 177.34 | 0.0367 | 260/310/350 |
| 400 kcmil | 0.6325 in | 202.68 | 0.0321 | 280/335/380 |
| 500 kcmil | 0.7071 in | 253.35 | 0.0258 | 320/380/430 |
| 600 kcmil | 0.7746 in | 304.02 | 0.0214 | 350/420/475 |
| 750 kcmil | 0.8660 in | 380.03 | 0.0171 | 400/475/535 |
Diameter is for a solid conductor. Ampacity from NEC Table 310.16; resistance from Chapter 9, Table 8.
How AWG works
American Wire Gauge numbers run backward: a smaller number is a thicker wire. Past 1 AWG the sizes become 1/0, 2/0, 3/0 and 4/0 ("one aught" to "four aught"), then switch to kcmil, thousands of circular mils. The diameter of gauge n is 0.005 × 92^((36 − n) ÷ 39) inches (ASTM B258).
Common questions
Which is bigger, 10 gauge or 12 gauge?
10 gauge. Lower AWG numbers are thicker. 10 AWG has about 59% more copper area than 12 AWG.