250 kcmil wire
250 kcmil copper carries 255 A at 75 °C. Below: its dimensions, ratings and how far it can run before voltage drop becomes a problem.
Maximum distance
Fill in the circuit, then press the button.
250 kcmil specifications
| Property | Value |
|---|---|
| Diameter, solid | 0.5000 in (12.70 mm) |
| Area | 250,000 cmil (126.67 mm²) |
| Resistance, copper | 0.0515 Ω per 1,000 ft |
| Resistance, aluminum | 0.0847 Ω per 1,000 ft |
| Copper ampacity | 215 / 255 / 290 A at 60 / 75 / 90 °C |
| Aluminum ampacity | 170 / 205 / 230 A |
| Largest breaker | 250 A at 75 °C |
Ampacity: NEC Table 310.16. Resistance: Chapter 9, Table 8, stranded, 75 °C.
How far 250 kcmil can run
One-way distance at 3% and 5% drop.
| Load | 240 V, 3% | 240 V, 5% |
|---|---|---|
| 62 A | 1,127 ft | 1,879 ft |
| 125 A | 559 ft | 932 ft |
| 200 A | 349 ft | 582 ft |
| 250 A | 279 ft | 466 ft |
Copper, single-phase.
Common questions
How many amps can 250 kcmil carry?
215 A at 60 °C, 255 A at 75 °C and 290 A at 90 °C for copper in conduit or cable with no more than three current-carrying conductors at 30 °C.
What is the diameter of 250 kcmil?
0.5000 in (12.70 mm) for a solid conductor. Stranded wire is slightly larger, and the insulation adds more.