Voltage Drop Calculator

HomeWire sizeWire gauge

250 kcmil wire

250 kcmil copper carries 255 A at 75 °C. Below: its dimensions, ratings and how far it can run before voltage drop becomes a problem.

V
A
%

Maximum distance

Fill in the circuit, then press the button.

250 kcmil specifications

PropertyValue
Diameter, solid0.5000 in (12.70 mm)
Area250,000 cmil (126.67 mm²)
Resistance, copper0.0515 Ω per 1,000 ft
Resistance, aluminum0.0847 Ω per 1,000 ft
Copper ampacity215 / 255 / 290 A at 60 / 75 / 90 °C
Aluminum ampacity170 / 205 / 230 A
Largest breaker250 A at 75 °C

Ampacity: NEC Table 310.16. Resistance: Chapter 9, Table 8, stranded, 75 °C.

How far 250 kcmil can run

One-way distance at 3% and 5% drop.

Load240 V, 3%240 V, 5%
62 A1,127 ft1,879 ft
125 A559 ft932 ft
200 A349 ft582 ft
250 A279 ft466 ft

Copper, single-phase.

What 250 kcmil is used for

250 kcmil copper is the usual choice for 225 to 255 A feeders. Neighboring sizes: 4/0 AWG, 300 kcmil.

Common questions

How many amps can 250 kcmil carry?

215 A at 60 °C, 255 A at 75 °C and 290 A at 90 °C for copper in conduit or cable with no more than three current-carrying conductors at 30 °C.

What is the diameter of 250 kcmil?

0.5000 in (12.70 mm) for a solid conductor. Stranded wire is slightly larger, and the insulation adds more.

Sources

  • NFPA 70, National Electrical Code, 2023 edition (https://www.nfpa.org/codes-and-standards/nfpa-70-standard-development/70)