Voltage Drop Calculator

HomeWire sizeWire gauge

4/0 AWG wire

4/0 AWG copper carries 230 A at 75 °C. Below: its dimensions, ratings and how far it can run before voltage drop becomes a problem.

V
A
%

Maximum distance

Fill in the circuit, then press the button.

4/0 AWG specifications

PropertyValue
Diameter, solid0.4600 in (11.68 mm)
Area211,600 cmil (107.22 mm²)
Resistance, copper0.0608 Ω per 1,000 ft
Resistance, aluminum0.1 Ω per 1,000 ft
Copper ampacity195 / 230 / 260 A at 60 / 75 / 90 °C
Aluminum ampacity150 / 180 / 205 A
Largest breaker225 A at 75 °C

Ampacity: NEC Table 310.16. Resistance: Chapter 9, Table 8, stranded, 75 °C.

How far 4/0 AWG can run

One-way distance at 3% and 5% drop.

Load240 V, 3%240 V, 5%
56 A1,057 ft1,762 ft
112 A528 ft881 ft
180 A328 ft548 ft
225 A263 ft438 ft

Copper, single-phase.

What 4/0 AWG is used for

4/0 AWG copper is the usual choice for 200 to 230 A feeders, and 200 A aluminum services. Neighboring sizes: 3/0 AWG, 250 kcmil.

Common questions

How many amps can 4/0 AWG carry?

195 A at 60 °C, 230 A at 75 °C and 260 A at 90 °C for copper in conduit or cable with no more than three current-carrying conductors at 30 °C.

What is the diameter of 4/0 AWG?

0.4600 in (11.68 mm) for a solid conductor. Stranded wire is slightly larger, and the insulation adds more.

Sources

  • NFPA 70, National Electrical Code, 2023 edition (https://www.nfpa.org/codes-and-standards/nfpa-70-standard-development/70)