4/0 AWG wire
4/0 AWG copper carries 230 A at 75 °C. Below: its dimensions, ratings and how far it can run before voltage drop becomes a problem.
Maximum distance
Fill in the circuit, then press the button.
4/0 AWG specifications
| Property | Value |
|---|---|
| Diameter, solid | 0.4600 in (11.68 mm) |
| Area | 211,600 cmil (107.22 mm²) |
| Resistance, copper | 0.0608 Ω per 1,000 ft |
| Resistance, aluminum | 0.1 Ω per 1,000 ft |
| Copper ampacity | 195 / 230 / 260 A at 60 / 75 / 90 °C |
| Aluminum ampacity | 150 / 180 / 205 A |
| Largest breaker | 225 A at 75 °C |
Ampacity: NEC Table 310.16. Resistance: Chapter 9, Table 8, stranded, 75 °C.
How far 4/0 AWG can run
One-way distance at 3% and 5% drop.
| Load | 240 V, 3% | 240 V, 5% |
|---|---|---|
| 56 A | 1,057 ft | 1,762 ft |
| 112 A | 528 ft | 881 ft |
| 180 A | 328 ft | 548 ft |
| 225 A | 263 ft | 438 ft |
Copper, single-phase.
Common questions
How many amps can 4/0 AWG carry?
195 A at 60 °C, 230 A at 75 °C and 260 A at 90 °C for copper in conduit or cable with no more than three current-carrying conductors at 30 °C.
What is the diameter of 4/0 AWG?
0.4600 in (11.68 mm) for a solid conductor. Stranded wire is slightly larger, and the insulation adds more.
Related calculators