3/0 AWG wire

3/0 AWG copper carries 200 A at 75 °C. Below: its dimensions, ratings and how far it can run before voltage drop becomes a problem.

V
A
%

Maximum distance

Fill in the circuit, then press the button.

3/0 AWG specifications

PropertyValue
Diameter, solid0.4096 in (10.40 mm)
Area167,800 cmil (85.02 mm²)
Resistance, copper0.0766 Ω per 1,000 ft
Resistance, aluminum0.126 Ω per 1,000 ft
Copper ampacity165 / 200 / 225 A at 60 / 75 / 90 °C
Aluminum ampacity130 / 155 / 175 A
Largest breaker200 A at 75 °C

Ampacity: NEC Table 310.16. Resistance: Chapter 9, Table 8, stranded, 75 °C.

How far 3/0 AWG can run

One-way distance at 3% and 5% drop.

Load240 V, 3%240 V, 5%
50 A939 ft1,566 ft
100 A469 ft783 ft
160 A293 ft489 ft
200 A234 ft391 ft

Copper, single-phase.

What 3/0 AWG is used for

3/0 AWG copper is the usual choice for 200 A feeders. Neighboring sizes: 2/0 AWG, 4/0 AWG.

Common questions

How many amps can 3/0 AWG carry?

165 A at 60 °C, 200 A at 75 °C and 225 A at 90 °C for copper in conduit or cable with no more than three current-carrying conductors at 30 °C.

What is the diameter of 3/0 AWG?

0.4096 in (10.40 mm) for a solid conductor. Stranded wire is slightly larger, and the insulation adds more.