2/0 AWG wire
2/0 AWG copper carries 175 A at 75 °C. Below: its dimensions, ratings and how far it can run before voltage drop becomes a problem.
Maximum distance
Fill in the circuit, then press the button.
2/0 AWG specifications
| Property | Value |
|---|---|
| Diameter, solid | 0.3648 in (9.27 mm) |
| Area | 133,100 cmil (67.44 mm²) |
| Resistance, copper | 0.0967 Ω per 1,000 ft |
| Resistance, aluminum | 0.159 Ω per 1,000 ft |
| Copper ampacity | 145 / 175 / 195 A at 60 / 75 / 90 °C |
| Aluminum ampacity | 115 / 135 / 150 A |
| Largest breaker | 175 A at 75 °C |
Ampacity: NEC Table 310.16. Resistance: Chapter 9, Table 8, stranded, 75 °C.
How far 2/0 AWG can run
One-way distance at 3% and 5% drop.
| Load | 240 V, 3% | 240 V, 5% |
|---|---|---|
| 44 A | 846 ft | 1,410 ft |
| 88 A | 423 ft | 705 ft |
| 140 A | 265 ft | 443 ft |
| 175 A | 212 ft | 354 ft |
Copper, single-phase.
Common questions
How many amps can 2/0 AWG carry?
145 A at 60 °C, 175 A at 75 °C and 195 A at 90 °C for copper in conduit or cable with no more than three current-carrying conductors at 30 °C.
What is the diameter of 2/0 AWG?
0.3648 in (9.27 mm) for a solid conductor. Stranded wire is slightly larger, and the insulation adds more.
Related calculators
Sources
- NFPA 70, National Electrical Code, 2023 edition (https://www.nfpa.org/codes-and-standards/nfpa-70-standard-development/70)