Voltage Drop Calculator

HomeWire sizeWire gauge

1/0 AWG wire

1/0 AWG copper carries 150 A at 75 °C. Below: its dimensions, ratings and how far it can run before voltage drop becomes a problem.

V
A
%

Maximum distance

Fill in the circuit, then press the button.

1/0 AWG specifications

PropertyValue
Diameter, solid0.3250 in (8.25 mm)
Area105,600 cmil (53.51 mm²)
Resistance, copper0.122 Ω per 1,000 ft
Resistance, aluminum0.201 Ω per 1,000 ft
Copper ampacity125 / 150 / 170 A at 60 / 75 / 90 °C
Aluminum ampacity100 / 120 / 135 A
Largest breaker150 A at 75 °C

Ampacity: NEC Table 310.16. Resistance: Chapter 9, Table 8, stranded, 75 °C.

How far 1/0 AWG can run

One-way distance at 3% and 5% drop.

Load240 V, 3%240 V, 5%
38 A776 ft1,294 ft
75 A393 ft655 ft
120 A245 ft409 ft
150 A196 ft327 ft

Copper, single-phase.

What 1/0 AWG is used for

1/0 AWG copper is the usual choice for 125 to 150 A feeders and services. Neighboring sizes: 1 AWG, 2/0 AWG.

Common questions

How many amps can 1/0 AWG carry?

125 A at 60 °C, 150 A at 75 °C and 170 A at 90 °C for copper in conduit or cable with no more than three current-carrying conductors at 30 °C.

What is the diameter of 1/0 AWG?

0.3250 in (8.25 mm) for a solid conductor. Stranded wire is slightly larger, and the insulation adds more.

Sources

  • NFPA 70, National Electrical Code, 2023 edition (https://www.nfpa.org/codes-and-standards/nfpa-70-standard-development/70)