1 AWG wire
1 AWG copper carries 130 A at 75 °C. Below: its dimensions, ratings and how far it can run before voltage drop becomes a problem.
Maximum distance
Fill in the circuit, then press the button.
1 AWG specifications
| Property | Value |
|---|---|
| Diameter, solid | 0.2893 in (7.35 mm) |
| Area | 83,690 cmil (42.41 mm²) |
| Resistance, copper | 0.154 Ω per 1,000 ft |
| Resistance, aluminum | 0.253 Ω per 1,000 ft |
| Copper ampacity | 110 / 130 / 145 A at 60 / 75 / 90 °C |
| Aluminum ampacity | 85 / 100 / 115 A |
| Largest breaker | 125 A at 75 °C |
Ampacity: NEC Table 310.16. Resistance: Chapter 9, Table 8, stranded, 75 °C.
How far 1 AWG can run
One-way distance at 3% and 5% drop.
| Load | 240 V, 3% | 240 V, 5% |
|---|---|---|
| 31 A | 754 ft | 1,256 ft |
| 62 A | 377 ft | 628 ft |
| 100 A | 233 ft | 389 ft |
| 125 A | 187 ft | 311 ft |
Copper, single-phase.
Common questions
How many amps can 1 AWG carry?
110 A at 60 °C, 130 A at 75 °C and 145 A at 90 °C for copper in conduit or cable with no more than three current-carrying conductors at 30 °C.
What is the diameter of 1 AWG?
0.2893 in (7.35 mm) for a solid conductor. Stranded wire is slightly larger, and the insulation adds more.
Related calculators
Sources
- NFPA 70, National Electrical Code, 2023 edition (https://www.nfpa.org/codes-and-standards/nfpa-70-standard-development/70)