Wire ampacity chart
Enter the breaker or load current to get the minimum size, or read the full ampacity table below.
Minimum wire
Fill in the circuit, then press the button.
Copper
| Size | 60 °C | 75 °C | 90 °C |
|---|---|---|---|
| 14 AWG | 15 A | 20 A | 25 A |
| 12 AWG | 20 A | 25 A | 30 A |
| 10 AWG | 30 A | 35 A | 40 A |
| 8 AWG | 40 A | 50 A | 55 A |
| 6 AWG | 55 A | 65 A | 75 A |
| 4 AWG | 70 A | 85 A | 95 A |
| 3 AWG | 85 A | 100 A | 115 A |
| 2 AWG | 95 A | 115 A | 130 A |
| 1 AWG | 110 A | 130 A | 145 A |
| 1/0 AWG | 125 A | 150 A | 170 A |
| 2/0 AWG | 145 A | 175 A | 195 A |
| 3/0 AWG | 165 A | 200 A | 225 A |
| 4/0 AWG | 195 A | 230 A | 260 A |
| 250 kcmil | 215 A | 255 A | 290 A |
| 300 kcmil | 240 A | 285 A | 320 A |
| 350 kcmil | 260 A | 310 A | 350 A |
| 400 kcmil | 280 A | 335 A | 380 A |
| 500 kcmil | 320 A | 380 A | 430 A |
| 600 kcmil | 350 A | 420 A | 475 A |
| 750 kcmil | 400 A | 475 A | 535 A |
Aluminum and copper-clad aluminum
| Size | 60 °C | 75 °C | 90 °C |
|---|---|---|---|
| 12 AWG | 15 A | 20 A | 25 A |
| 10 AWG | 25 A | 30 A | 35 A |
| 8 AWG | 35 A | 40 A | 45 A |
| 6 AWG | 40 A | 50 A | 55 A |
| 4 AWG | 55 A | 65 A | 75 A |
| 3 AWG | 65 A | 75 A | 85 A |
| 2 AWG | 75 A | 90 A | 100 A |
| 1 AWG | 85 A | 100 A | 115 A |
| 1/0 AWG | 100 A | 120 A | 135 A |
| 2/0 AWG | 115 A | 135 A | 150 A |
| 3/0 AWG | 130 A | 155 A | 175 A |
| 4/0 AWG | 150 A | 180 A | 205 A |
| 250 kcmil | 170 A | 205 A | 230 A |
| 300 kcmil | 195 A | 230 A | 260 A |
| 350 kcmil | 210 A | 250 A | 280 A |
| 400 kcmil | 225 A | 270 A | 305 A |
| 500 kcmil | 260 A | 310 A | 350 A |
| 600 kcmil | 285 A | 340 A | 385 A |
| 750 kcmil | 320 A | 385 A | 435 A |
Reading the table
Values assume no more than three current-carrying conductors in a raceway, cable or the earth, at 30 °C ambient. Hotter spaces and more conductors reduce the figures; use the derating calculator. Terminations limit you to the 60 °C column on circuits of 100 A or less unless the equipment is marked 75 °C (110.14(C)).
Common questions
Which temperature column should I use?
The lowest-rated part of the circuit sets it. NM-B cable uses 60 °C. THHN/THWN-2 in conduit landing on 75 °C breakers and lugs uses 75 °C. The 90 °C column is for derating calculations only.
Related calculators
Sources
- NFPA 70, National Electrical Code, 2023 edition (https://www.nfpa.org/codes-and-standards/nfpa-70-standard-development/70)