Wire ampacity chart

Enter the breaker or load current to get the minimum size, or read the full ampacity table below.

A

Minimum wire

Fill in the circuit, then press the button.

Copper

Size60 °C75 °C90 °C
14 AWG15 A20 A25 A
12 AWG20 A25 A30 A
10 AWG30 A35 A40 A
8 AWG40 A50 A55 A
6 AWG55 A65 A75 A
4 AWG70 A85 A95 A
3 AWG85 A100 A115 A
2 AWG95 A115 A130 A
1 AWG110 A130 A145 A
1/0 AWG125 A150 A170 A
2/0 AWG145 A175 A195 A
3/0 AWG165 A200 A225 A
4/0 AWG195 A230 A260 A
250 kcmil215 A255 A290 A
300 kcmil240 A285 A320 A
350 kcmil260 A310 A350 A
400 kcmil280 A335 A380 A
500 kcmil320 A380 A430 A
600 kcmil350 A420 A475 A
750 kcmil400 A475 A535 A

Aluminum and copper-clad aluminum

Size60 °C75 °C90 °C
12 AWG15 A20 A25 A
10 AWG25 A30 A35 A
8 AWG35 A40 A45 A
6 AWG40 A50 A55 A
4 AWG55 A65 A75 A
3 AWG65 A75 A85 A
2 AWG75 A90 A100 A
1 AWG85 A100 A115 A
1/0 AWG100 A120 A135 A
2/0 AWG115 A135 A150 A
3/0 AWG130 A155 A175 A
4/0 AWG150 A180 A205 A
250 kcmil170 A205 A230 A
300 kcmil195 A230 A260 A
350 kcmil210 A250 A280 A
400 kcmil225 A270 A305 A
500 kcmil260 A310 A350 A
600 kcmil285 A340 A385 A
750 kcmil320 A385 A435 A

Reading the table

Values assume no more than three current-carrying conductors in a raceway, cable or the earth, at 30 °C ambient. Hotter spaces and more conductors reduce the figures; use the derating calculator. Terminations limit you to the 60 °C column on circuits of 100 A or less unless the equipment is marked 75 °C (110.14(C)).

Common questions

Which temperature column should I use?

The lowest-rated part of the circuit sets it. NM-B cable uses 60 °C. THHN/THWN-2 in conduit landing on 75 °C breakers and lugs uses 75 °C. The 90 °C column is for derating calculations only.

Sources

  • NFPA 70, National Electrical Code, 2023 edition (https://www.nfpa.org/codes-and-standards/nfpa-70-standard-development/70)