Heat and crowding cut how much current a wire can carry. Enter the wire, insulation rating, ambient temperature and number of current-carrying conductors.

Count hots and any neutral that carries unbalanced current. Grounds don't count.

Adjusted ampacity

Fill in the circuit, then press the button.

Adjustment for more than three conductors

Current-carrying conductorsFactor
4–680%
7–970%
10–2050%
21–3045%
31–4040%
41 and up35%

Table 310.15(C)(1).

What counts as current-carrying

  • Every hot conductor counts.
  • A neutral on a balanced 120/240 V circuit does not count; on a 3-phase 4-wire wye circuit with mostly electronic or LED loads it does (310.15(E)).
  • Equipment grounds never count.
  • Raceway sections 24 in or shorter are exempt (310.15(C)(1)(b)).

Common questions

Can I derate from the 90 °C column?

Yes, with 90 °C insulation such as THHN/THWN-2. The adjusted result still may not exceed the ampacity of the lowest-rated termination, usually 75 °C.