Ampacity derating calculator
Heat and crowding cut how much current a wire can carry. Enter the wire, insulation rating, ambient temperature and number of current-carrying conductors.
Adjusted ampacity
Fill in the circuit, then press the button.
Adjustment for more than three conductors
| Current-carrying conductors | Factor |
|---|---|
| 4–6 | 80% |
| 7–9 | 70% |
| 10–20 | 50% |
| 21–30 | 45% |
| 31–40 | 40% |
| 41 and up | 35% |
Table 310.15(C)(1).
What counts as current-carrying
- Every hot conductor counts.
- A neutral on a balanced 120/240 V circuit does not count; on a 3-phase 4-wire wye circuit with mostly electronic or LED loads it does (310.15(E)).
- Equipment grounds never count.
- Raceway sections 24 in or shorter are exempt (310.15(C)(1)(b)).
Common questions
Can I derate from the 90 °C column?
Yes, with 90 °C insulation such as THHN/THWN-2. The adjusted result still may not exceed the ampacity of the lowest-rated termination, usually 75 °C.
Related calculators
Sources
- NFPA 70, National Electrical Code, 2023 edition (https://www.nfpa.org/codes-and-standards/nfpa-70-standard-development/70)