Each wire, device and clamp in a box takes a volume allowance. Enter what goes in the box.

Each device counts as two wires of the largest size connected to it.

Box volume

Fill in the circuit, then press the button.

Volume per conductor

SizeVolume
18 AWG1.5 in³
16 AWG1.75 in³
14 AWG2.0 in³
12 AWG2.25 in³
10 AWG2.5 in³
8 AWG3.0 in³
6 AWG5.0 in³

Table 314.16(B).

Counting rules

  • Each wire that enters and ends or splices in the box: one allowance.
  • A wire passing through unbroken: one allowance.
  • Pigtails and wires that start and end in the box: none.
  • All equipment grounds together: one allowance, plus a quarter allowance for each ground beyond four (314.16(B)(5)).
  • All internal clamps together: one allowance.

Common questions

How many 12 gauge wires in a 18 cubic inch box?

Eight allowances at 2.25 in³: for example two 12/2 cables (four wires) with one receptacle (two) plus grounds (one) and clamps (one).

Sources

  • NFPA 70, National Electrical Code, 2023 edition (https://www.nfpa.org/codes-and-standards/nfpa-70-standard-development/70)