Box fill calculator
Each wire, device and clamp in a box takes a volume allowance. Enter what goes in the box.
Box volume
Fill in the circuit, then press the button.
Volume per conductor
| Size | Volume |
|---|---|
| 18 AWG | 1.5 in³ |
| 16 AWG | 1.75 in³ |
| 14 AWG | 2.0 in³ |
| 12 AWG | 2.25 in³ |
| 10 AWG | 2.5 in³ |
| 8 AWG | 3.0 in³ |
| 6 AWG | 5.0 in³ |
Table 314.16(B).
Counting rules
- Each wire that enters and ends or splices in the box: one allowance.
- A wire passing through unbroken: one allowance.
- Pigtails and wires that start and end in the box: none.
- All equipment grounds together: one allowance, plus a quarter allowance for each ground beyond four (314.16(B)(5)).
- All internal clamps together: one allowance.
Common questions
How many 12 gauge wires in a 18 cubic inch box?
Eight allowances at 2.25 in³: for example two 12/2 cables (four wires) with one receptacle (two) plus grounds (one) and clamps (one).
Related calculators
Sources
- NFPA 70, National Electrical Code, 2023 edition (https://www.nfpa.org/codes-and-standards/nfpa-70-standard-development/70)