EMT conduit fill chart
Use the chart for a single wire size, or the calculator for a mix.
EMT size
Fill in the circuit, then press the button.
Maximum THHN in EMT
| Trade size | 14 | 12 | 10 | 8 | 6 | 4 | 2 | 1/0 |
|---|---|---|---|---|---|---|---|---|
| 1/2 in | 12 | 9 | 5 | 3 | 1 | 1 | 1 | 0 |
| 3/4 in | 22 | 16 | 10 | 6 | 4 | 2 | 1 | 1 |
| 1 in | 35 | 26 | 16 | 9 | 7 | 4 | 3 | 1 |
| 1-1/4 in | 61 | 45 | 28 | 16 | 12 | 7 | 5 | 3 |
| 1-1/2 in | 84 | 61 | 38 | 22 | 16 | 10 | 7 | 4 |
| 2 in | 138 | 101 | 63 | 36 | 26 | 16 | 11 | 7 |
| 2-1/2 in | 241 | 176 | 111 | 64 | 46 | 28 | 20 | 12 |
| 3 in | 364 | 266 | 167 | 96 | 69 | 43 | 30 | 19 |
| 3-1/2 in | 476 | 347 | 219 | 126 | 91 | 56 | 40 | 25 |
| 4 in | 608 | 443 | 279 | 161 | 116 | 71 | 51 | 32 |
Maximum THHN/THWN-2 conductors of one size in EMT, from Chapter 9, Tables 1, 4 and 5, with the Note 7 rounding rule.
EMT trade sizes
| Trade size | Inside area | 40% area |
|---|---|---|
| 1/2 in | 0.304 in² | 0.122 in² |
| 3/4 in | 0.533 in² | 0.213 in² |
| 1 in | 0.864 in² | 0.346 in² |
| 1-1/4 in | 1.496 in² | 0.598 in² |
| 1-1/2 in | 2.036 in² | 0.814 in² |
| 2 in | 3.356 in² | 1.342 in² |
| 2-1/2 in | 5.858 in² | 2.343 in² |
| 3 in | 8.846 in² | 3.538 in² |
| 3-1/2 in | 11.545 in² | 4.618 in² |
| 4 in | 14.753 in² | 5.901 in² |
Common questions
How many 12 AWG wires fit in 1/2 in EMT?
Nine THHN, from 0.304 × 40% ÷ 0.0133 = 9.1. Ampacity derating applies above three current-carrying conductors.
Related calculators
Sources
- NFPA 70, National Electrical Code, 2023 edition (https://www.nfpa.org/codes-and-standards/nfpa-70-standard-development/70)