EMT conduit fill chart

Use the chart for a single wire size, or the calculator for a mix.

EMT size

Fill in the circuit, then press the button.

Maximum THHN in EMT

Trade size14121086421/0
1/2 in129531110
3/4 in22161064211
1 in35261697431
1-1/4 in6145281612753
1-1/2 in84613822161074
2 in13810163362616117
2-1/2 in2411761116446282012
3 in3642661679669433019
3-1/2 in47634721912691564025
4 in608443279161116715132

Maximum THHN/THWN-2 conductors of one size in EMT, from Chapter 9, Tables 1, 4 and 5, with the Note 7 rounding rule.

EMT trade sizes

Trade sizeInside area40% area
1/2 in0.304 in²0.122 in²
3/4 in0.533 in²0.213 in²
1 in0.864 in²0.346 in²
1-1/4 in1.496 in²0.598 in²
1-1/2 in2.036 in²0.814 in²
2 in3.356 in²1.342 in²
2-1/2 in5.858 in²2.343 in²
3 in8.846 in²3.538 in²
3-1/2 in11.545 in²4.618 in²
4 in14.753 in²5.901 in²

Common questions

How many 12 AWG wires fit in 1/2 in EMT?

Nine THHN, from 0.304 × 40% ÷ 0.0133 = 9.1. Ampacity derating applies above three current-carrying conductors.

Sources

  • NFPA 70, National Electrical Code, 2023 edition (https://www.nfpa.org/codes-and-standards/nfpa-70-standard-development/70)