Breaker size calculator
Enter the load and choose whether it runs continuously. You get the breaker, the wire that goes with it and the ground.
Breaker and wire
Fill in the circuit, then press the button.
Standard breaker sizes
NEC 240.6(A) lists standard ratings: 15, 20, 25, 30, 35, 40, 45, 50, 60, 70, 80, 90, 100, 110, 125, 150, 175, 200, 225, 250, 300, 350, 400, 450, 500, 600, 700, 800 A. Where the wire's ampacity falls between standard sizes, 240.4(B) allows the next size up for circuits of 800 A or less, except multioutlet receptacle circuits.
Wire for each breaker
| Breaker | Copper 60 °C | Copper 75 °C | Aluminum 75 °C |
|---|---|---|---|
| 15 A | 14 AWG | 14 AWG | 12 AWG |
| 20 A | 12 AWG | 12 AWG | 10 AWG |
| 30 A | 10 AWG | 10 AWG | 8 AWG |
| 40 A | 8 AWG | 8 AWG | 8 AWG |
| 50 A | 6 AWG | 8 AWG | 6 AWG |
| 60 A | 4 AWG | 6 AWG | 4 AWG |
| 70 A | 4 AWG | 4 AWG | 3 AWG |
| 80 A | 3 AWG | 4 AWG | 2 AWG |
| 90 A | 2 AWG | 3 AWG | 2 AWG |
| 100 A | 1 AWG | 3 AWG | 1 AWG |
| 125 A | 1/0 AWG | 1 AWG | 2/0 AWG |
| 150 A | 3/0 AWG | 1/0 AWG | 3/0 AWG |
| 200 A | 250 kcmil | 3/0 AWG | 250 kcmil |
Common questions
What breaker for 5,000 watts at 240 V?
20.8 A noncontinuous needs a 25 A breaker; as a continuous load, 26 A needs a 30 A breaker.
Related calculators
Sources
- NFPA 70, National Electrical Code, 2023 edition (https://www.nfpa.org/codes-and-standards/nfpa-70-standard-development/70)