Voltage Drop Calculator

HomeCode tools

Breaker size calculator

Enter the load and choose whether it runs continuously. You get the breaker, the wire that goes with it and the ground.

V
One way from the panel. Enter 0 to skip voltage drop.
%

Breaker and wire

Fill in the circuit, then press the button.

Standard breaker sizes

NEC 240.6(A) lists standard ratings: 15, 20, 25, 30, 35, 40, 45, 50, 60, 70, 80, 90, 100, 110, 125, 150, 175, 200, 225, 250, 300, 350, 400, 450, 500, 600, 700, 800 A. Where the wire's ampacity falls between standard sizes, 240.4(B) allows the next size up for circuits of 800 A or less, except multioutlet receptacle circuits.

Wire for each breaker

BreakerCopper 60 °CCopper 75 °CAluminum 75 °C
15 A14 AWG14 AWG12 AWG
20 A12 AWG12 AWG10 AWG
30 A10 AWG10 AWG8 AWG
40 A8 AWG8 AWG8 AWG
50 A6 AWG8 AWG6 AWG
60 A4 AWG6 AWG4 AWG
70 A4 AWG4 AWG3 AWG
80 A3 AWG4 AWG2 AWG
90 A2 AWG3 AWG2 AWG
100 A1 AWG3 AWG1 AWG
125 A1/0 AWG1 AWG2/0 AWG
150 A3/0 AWG1/0 AWG3/0 AWG
200 A250 kcmil3/0 AWG250 kcmil

Common questions

What breaker for 5,000 watts at 240 V?

20.8 A noncontinuous needs a 25 A breaker; as a continuous load, 26 A needs a 30 A breaker.

Sources

  • NFPA 70, National Electrical Code, 2023 edition (https://www.nfpa.org/codes-and-standards/nfpa-70-standard-development/70)