Breaker size for a wire
Pick the wire to see its ratings and the largest breaker it may be protected by.
Wire ratings
Fill in the circuit, then press the button.
Largest breaker by wire
| Wire | Copper, 60 °C | Copper, 75 °C | Aluminum, 75 °C |
|---|---|---|---|
| 14 AWG | 15 A | 15 A | — |
| 12 AWG | 20 A | 20 A | 15 A |
| 10 AWG | 30 A | 30 A | 25 A |
| 8 AWG | 40 A | 50 A | 40 A |
| 6 AWG | 60 A | 70 A | 50 A |
| 4 AWG | 70 A | 90 A | 70 A |
| 3 AWG | 90 A | 100 A | 80 A |
| 2 AWG | 100 A | 125 A | 90 A |
| 1 AWG | 110 A | 150 A | 100 A |
| 1/0 AWG | 125 A | 150 A | 125 A |
| 2/0 AWG | 150 A | 175 A | 150 A |
| 3/0 AWG | 175 A | 200 A | 175 A |
| 4/0 AWG | 200 A | 250 A | 200 A |
| 250 kcmil | 225 A | 300 A | 225 A |
| 350 kcmil | 300 A | 350 A | 250 A |
| 500 kcmil | 350 A | 400 A | 350 A |
Where the ampacity is not a standard size, the next size up is shown (240.4(B)); that is not allowed on multioutlet receptacle circuits or above 800 A.
Exceptions
Motor, compressor, welder and some HVAC circuits follow their own articles and may use a larger breaker than the wire's ampacity, because separate overload devices protect the wire.
Common questions
Can 10 gauge wire go on a 40 amp breaker?
Not for ordinary circuits. 240.4(D) limits 10 AWG copper to 30 A. A motor or AC unit whose nameplate MOCP is 40 A is an exception.