Motor wire size calculator

Motor circuits use the NEC tables for full-load current, not the nameplate, for sizing wire and breakers. Pick horsepower, phase and voltage.

One way from the panel to the motor. Enter 0 to skip voltage drop.
%
Used for voltage drop. Leave blank to use the NEC table current.
A

Motor circuit

Fill in the circuit, then press the button.

Three-phase full-load current

HP208 V230 V460 V575 V
1/2 HP2.4 A2.2 A1.1 A0.9 A
3/4 HP3.5 A3.2 A1.6 A1.3 A
1 HP4.6 A4.2 A2.1 A1.7 A
1-1/2 HP6.6 A6.0 A3.0 A2.4 A
2 HP7.5 A6.8 A3.4 A2.7 A
3 HP10.6 A9.6 A4.8 A3.9 A
5 HP16.7 A15.2 A7.6 A6.1 A
7-1/2 HP24.2 A22 A11 A9 A
10 HP30.8 A28 A14 A11 A
15 HP46.2 A42 A21 A17 A
20 HP59.4 A54 A27 A22 A
25 HP74.8 A68 A34 A27 A
30 HP88 A80 A40 A32 A
40 HP114 A104 A52 A41 A
50 HP143 A130 A65 A52 A
60 HP169 A154 A77 A62 A
75 HP211 A192 A96 A77 A
100 HP273 A248 A124 A99 A

NEC Table 430.250.

Single-phase full-load current

HP115 V208 V230 V
1/6 HP4.4 A2.4 A2.2 A
1/4 HP5.8 A3.2 A2.9 A
1/3 HP7.2 A4.0 A3.6 A
1/2 HP9.8 A5.4 A4.9 A
3/4 HP13.8 A7.6 A6.9 A
1 HP16 A8.8 A8 A
1-1/2 HP20 A11.0 A10 A
2 HP24 A13.2 A12 A
3 HP34 A18.7 A17 A
5 HP56 A30.8 A28 A
7-1/2 HP80 A44.0 A40 A
10 HP100 A55.0 A50 A

NEC Table 430.248.

Common questions

Why not use nameplate amps?

430.6(A)(1) requires the table current for conductor and short-circuit protection sizing. The nameplate is used for overload protection.

Sources

  • NFPA 70, National Electrical Code, 2023 edition (https://www.nfpa.org/codes-and-standards/nfpa-70-standard-development/70)