Ambient temperature correction
Table 310.16 assumes 30 °C (86 °F). Wire in a hot attic or a boiler room carries less. Enter the temperature and the wire.
Corrected ampacity
Fill in the circuit, then press the button.
Correction factors
| Ambient | 60 °C | 75 °C | 90 °C |
|---|---|---|---|
| 10 °C or less | 1.29 | 1.20 | 1.15 |
| 11–15 °C (51–59 °F) | 1.22 | 1.15 | 1.12 |
| 16–20 °C (60–68 °F) | 1.15 | 1.11 | 1.08 |
| 21–25 °C (69–77 °F) | 1.08 | 1.05 | 1.04 |
| 26–30 °C (78–86 °F) | 1.00 | 1.00 | 1.00 |
| 31–35 °C (87–95 °F) | 0.91 | 0.94 | 0.96 |
| 36–40 °C (96–104 °F) | 0.82 | 0.88 | 0.91 |
| 41–45 °C (105–113 °F) | 0.71 | 0.82 | 0.87 |
| 46–50 °C (114–122 °F) | 0.58 | 0.75 | 0.82 |
| 51–55 °C (123–131 °F) | 0.41 | 0.67 | 0.76 |
| 56–60 °C (132–140 °F) | — | 0.58 | 0.71 |
| 61–65 °C (141–149 °F) | — | 0.47 | 0.65 |
| 66–70 °C (150–158 °F) | — | 0.33 | 0.58 |
| 71–75 °C (159–167 °F) | — | — | 0.50 |
| 76–80 °C (168–176 °F) | — | — | 0.41 |
| 81–85 °C (177–185 °F) | — | — | 0.29 |
Table 310.15(B)(1)(1), based on 30 °C.
Rooftops
Raceways or cables on or above a rooftop exposed to direct sun get a 33 °C (60 °F) temperature adder unless they are at least 7/8 in above the roof (310.15(B)(2)). Type XHHW-2 is exempt from the adder.
Common questions
What is the correction for 40 °C?
0.88 for 75 °C conductors and 0.91 for 90 °C conductors.