Voltage Drop Calculator

HomeCode tools

Ambient temperature correction

Table 310.16 assumes 30 °C (86 °F). Wire in a hot attic or a boiler room carries less. Enter the temperature and the wire.

Count hots and any neutral that carries unbalanced current. Grounds don't count.

Corrected ampacity

Fill in the circuit, then press the button.

Correction factors

Ambient60 °C75 °C90 °C
10 °C or less1.291.201.15
11–15 °C (51–59 °F)1.221.151.12
16–20 °C (60–68 °F)1.151.111.08
21–25 °C (69–77 °F)1.081.051.04
26–30 °C (78–86 °F)1.001.001.00
31–35 °C (87–95 °F)0.910.940.96
36–40 °C (96–104 °F)0.820.880.91
41–45 °C (105–113 °F)0.710.820.87
46–50 °C (114–122 °F)0.580.750.82
51–55 °C (123–131 °F)0.410.670.76
56–60 °C (132–140 °F)—0.580.71
61–65 °C (141–149 °F)—0.470.65
66–70 °C (150–158 °F)—0.330.58
71–75 °C (159–167 °F)——0.50
76–80 °C (168–176 °F)——0.41
81–85 °C (177–185 °F)——0.29

Table 310.15(B)(1)(1), based on 30 °C.

Rooftops

Raceways or cables on or above a rooftop exposed to direct sun get a 33 °C (60 °F) temperature adder unless they are at least 7/8 in above the roof (310.15(B)(2)). Type XHHW-2 is exempt from the adder.

Common questions

What is the correction for 40 °C?

0.88 for 75 °C conductors and 0.91 for 90 °C conductors.

Sources

  • NFPA 70, National Electrical Code, 2023 edition (https://www.nfpa.org/codes-and-standards/nfpa-70-standard-development/70)