80% rule for continuous loads

A continuous load runs three hours or more. Standard breakers may carry only 80% of their rating continuously, which is the same as sizing the circuit at 125% of the load.

V
One way from the panel. Enter 0 to skip voltage drop.
%

Circuit

Fill in the circuit, then press the button.

Continuous load by breaker

BreakerMax continuous loadAt 120 VAt 240 V
15 A12 A1,440 W2,880 W
20 A16 A1,920 W3,840 W
30 A24 A2,880 W5,760 W
40 A32 A3,840 W7,680 W
50 A40 A4,800 W9,600 W
60 A48 A5,760 W11,520 W
70 A56 A6,720 W13,440 W
80 A64 A7,680 W15,360 W
100 A80 A9,600 W19,200 W

Where it applies

Branch circuits (210.19(A) and 210.20(A)), feeders (215.2 and 215.3), EV chargers (625.41), water heaters (422.13), fixed electric heat (424.4) and PV circuits (690.8). Breakers listed for 100% continuous operation, usually large commercial frames, are the exception.

Common questions

Is the 80% rule in the NEC?

Not by that name. The code says the overcurrent device must be at least 125% of the continuous load, which works out to loading it to 80%.

Sources

  • NFPA 70, National Electrical Code, 2023 edition (https://www.nfpa.org/codes-and-standards/nfpa-70-standard-development/70)