80% rule for continuous loads
A continuous load runs three hours or more. Standard breakers may carry only 80% of their rating continuously, which is the same as sizing the circuit at 125% of the load.
Circuit
Fill in the circuit, then press the button.
Continuous load by breaker
| Breaker | Max continuous load | At 120 V | At 240 V |
|---|---|---|---|
| 15 A | 12 A | 1,440 W | 2,880 W |
| 20 A | 16 A | 1,920 W | 3,840 W |
| 30 A | 24 A | 2,880 W | 5,760 W |
| 40 A | 32 A | 3,840 W | 7,680 W |
| 50 A | 40 A | 4,800 W | 9,600 W |
| 60 A | 48 A | 5,760 W | 11,520 W |
| 70 A | 56 A | 6,720 W | 13,440 W |
| 80 A | 64 A | 7,680 W | 15,360 W |
| 100 A | 80 A | 9,600 W | 19,200 W |
Where it applies
Branch circuits (210.19(A) and 210.20(A)), feeders (215.2 and 215.3), EV chargers (625.41), water heaters (422.13), fixed electric heat (424.4) and PV circuits (690.8). Breakers listed for 100% continuous operation, usually large commercial frames, are the exception.
Common questions
Is the 80% rule in the NEC?
Not by that name. The code says the overcurrent device must be at least 125% of the continuous load, which works out to loading it to 80%.
Related calculators
Sources
- NFPA 70, National Electrical Code, 2023 edition (https://www.nfpa.org/codes-and-standards/nfpa-70-standard-development/70)