Transformer calculator
Enter the transformer kVA and voltages for full-load currents on both sides, plus the breakers and conductors.
Transformer
Fill in the circuit, then press the button.
Formulas
Single-phase: I = kVA × 1,000 ÷ V
Three-phase: I = kVA × 1,000 ÷ (1.732 × V)
Common questions
Why is the secondary breaker 125%?
Transformers are sized for their load, and that load is often continuous. 450.3(B) sets 125% of rated current as the maximum for primary-and-secondary protection at the secondary.