15 kVA transformer sizing
A 15 kVA three-phase transformer carries 42 A on a 208 V secondary and 18 A on a 480 V primary. Enter your voltages to size breakers and wire.
Transformer
Fill in the circuit, then press the button.
Full-load current
| Voltage | Current |
|---|---|
| 208 V | 41.6 A |
| 240 V | 36.1 A |
| 480 V | 18.0 A |
| 600 V | 14.4 A |
Protection and conductors
| Side | Current | Breaker (125%) | Copper (75 °C) | Aluminum (75 °C) |
|---|---|---|---|---|
| Primary 480 V | 18.0 A | 25 A | 10 AWG | 10 AWG |
| Secondary 208 V | 41.6 A | 60 A | 6 AWG | 4 AWG |
450.3(B) with primary and secondary protection. Secondary conductors also follow the tap rules in 240.21(C).
Common questions
How many amps is a 15 kVA transformer?
41.6 A at 208 V and 18.0 A at 480 V, three-phase.
Related calculators
Sources
- NFPA 70, National Electrical Code, 2023 edition (https://www.nfpa.org/codes-and-standards/nfpa-70-standard-development/70)