Horsepower to amps calculator

Choose the system and enter the value. The result includes the copper wire that carries the current.

V
%

Result

Fill in the circuit, then press the button.

Formula

I = HP × 746 ÷ (V × efficiency × PF), × 1/1.732 for three-phase

Power factor is 1 for resistive loads such as heaters and incandescent lights, and about 0.8 to 0.95 for motors and electronics. Leave it at 1 if you don't know it and the load is mostly heat.

Chart

HP115 V 1φ (table)230 V 1φ (table)460 V 3φ (table)
1/2 HP9.8 A4.9 A1.1 A
1 HP16 A8 A2.1 A
2 HP24 A12 A3.4 A
3 HP34 A17 A4.8 A
5 HP56 A28 A7.6 A
7-1/2 HP80 A40 A11 A
10 HP100 A50 A14 A
15 HP——21 A
25 HP——34 A
50 HP——65 A

NEC Tables 430.248 and 430.250, the values to use for wire and breaker sizing.

Common questions

Do I use 1.732 for three-phase?

Yes. In balanced three-phase power, P = 1.732 × V(line to line) × I × PF.

Sources

  • NFPA 70, National Electrical Code, 2023 edition (https://www.nfpa.org/codes-and-standards/nfpa-70-standard-development/70)