Horsepower to amps calculator
Choose the system and enter the value. The result includes the copper wire that carries the current.
Result
Fill in the circuit, then press the button.
Formula
I = HP × 746 ÷ (V × efficiency × PF), × 1/1.732 for three-phase
Power factor is 1 for resistive loads such as heaters and incandescent lights, and about 0.8 to 0.95 for motors and electronics. Leave it at 1 if you don't know it and the load is mostly heat.
Chart
| HP | 115 V 1φ (table) | 230 V 1φ (table) | 460 V 3φ (table) |
|---|---|---|---|
| 1/2 HP | 9.8 A | 4.9 A | 1.1 A |
| 1 HP | 16 A | 8 A | 2.1 A |
| 2 HP | 24 A | 12 A | 3.4 A |
| 3 HP | 34 A | 17 A | 4.8 A |
| 5 HP | 56 A | 28 A | 7.6 A |
| 7-1/2 HP | 80 A | 40 A | 11 A |
| 10 HP | 100 A | 50 A | 14 A |
| 15 HP | — | — | 21 A |
| 25 HP | — | — | 34 A |
| 50 HP | — | — | 65 A |
NEC Tables 430.248 and 430.250, the values to use for wire and breaker sizing.
Common questions
Do I use 1.732 for three-phase?
Yes. In balanced three-phase power, P = 1.732 × V(line to line) × I × PF.
Related calculators
Sources
- NFPA 70, National Electrical Code, 2023 edition (https://www.nfpa.org/codes-and-standards/nfpa-70-standard-development/70)