Voltage Drop Calculator

HomeConversions

kVA to amps calculator

Choose the system and enter the value. The result includes the copper wire that carries the current.

V
%

Result

Fill in the circuit, then press the button.

Formula

I = kVA × 1,000 ÷ V, or ÷ (1.732 × V) for three-phase

Power factor is 1 for resistive loads such as heaters and incandescent lights, and about 0.8 to 0.95 for motors and electronics. Leave it at 1 if you don't know it and the load is mostly heat.

Chart

kVA240 V 1φ208 V 3φ480 V 3φ
10 kVA41.7 A27.8 A12.0 A
15 kVA62.5 A41.6 A18.0 A
25 kVA104.2 A69.4 A30.1 A
30 kVA125.0 A83.3 A36.1 A
45 kVA187.5 A124.9 A54.1 A
75 kVA312.5 A208.2 A90.2 A
112.5 kVA468.8 A312.3 A135.3 A
150 kVA625.0 A416.4 A180.4 A
225 kVA937.5 A624.6 A270.6 A
300 kVA1250.0 A832.7 A360.9 A
500 kVA2083.3 A1387.9 A601.4 A

Common questions

Do I use 1.732 for three-phase?

Yes. In balanced three-phase power, P = 1.732 × V(line to line) × I × PF.

Sources

  • NFPA 70, National Electrical Code, 2023 edition (https://www.nfpa.org/codes-and-standards/nfpa-70-standard-development/70)