kVA to amps calculator
Choose the system and enter the value. The result includes the copper wire that carries the current.
Result
Fill in the circuit, then press the button.
Formula
I = kVA × 1,000 ÷ V, or ÷ (1.732 × V) for three-phase
Power factor is 1 for resistive loads such as heaters and incandescent lights, and about 0.8 to 0.95 for motors and electronics. Leave it at 1 if you don't know it and the load is mostly heat.
Chart
| kVA | 240 V 1φ | 208 V 3φ | 480 V 3φ |
|---|---|---|---|
| 10 kVA | 41.7 A | 27.8 A | 12.0 A |
| 15 kVA | 62.5 A | 41.6 A | 18.0 A |
| 25 kVA | 104.2 A | 69.4 A | 30.1 A |
| 30 kVA | 125.0 A | 83.3 A | 36.1 A |
| 45 kVA | 187.5 A | 124.9 A | 54.1 A |
| 75 kVA | 312.5 A | 208.2 A | 90.2 A |
| 112.5 kVA | 468.8 A | 312.3 A | 135.3 A |
| 150 kVA | 625.0 A | 416.4 A | 180.4 A |
| 225 kVA | 937.5 A | 624.6 A | 270.6 A |
| 300 kVA | 1250.0 A | 832.7 A | 360.9 A |
| 500 kVA | 2083.3 A | 1387.9 A | 601.4 A |
Common questions
Do I use 1.732 for three-phase?
Yes. In balanced three-phase power, P = 1.732 × V(line to line) × I × PF.