Voltage Drop Calculator

HomeConversions

Watts to amps calculator

Choose the system and enter the value. The result includes the copper wire that carries the current.

V
%

Result

Fill in the circuit, then press the button.

Formula

I = W ÷ V (DC or resistive AC), I = W ÷ (V × PF) for AC, I = W ÷ (1.732 × V × PF) for three-phase

Power factor is 1 for resistive loads such as heaters and incandescent lights, and about 0.8 to 0.95 for motors and electronics. Leave it at 1 if you don't know it and the load is mostly heat.

Chart

Watts120 V240 V
100 W0.83 A0.42 A
300 W2.50 A1.25 A
500 W4.17 A2.08 A
750 W6.25 A3.12 A
1,000 W8.33 A4.17 A
1,500 W12.50 A6.25 A
2,000 W16.67 A8.33 A
3,000 W25.00 A12.50 A
4,500 W37.50 A18.75 A
5,000 W41.67 A20.83 A
10,000 W83.33 A41.67 A

Power factor 1.

Common questions

Do I use 1.732 for three-phase?

Yes. In balanced three-phase power, P = 1.732 × V(line to line) × I × PF.

Sources

  • NFPA 70, National Electrical Code, 2023 edition (https://www.nfpa.org/codes-and-standards/nfpa-70-standard-development/70)