25 kVA transformer sizing
A 25 kVA single-phase transformer carries 104 A on a 240 V secondary and 52 A on a 480 V primary. Enter your voltages to size breakers and wire.
Transformer
Fill in the circuit, then press the button.
Full-load current
| Voltage | Current |
|---|---|
| 120 V | 208.3 A |
| 240 V | 104.2 A |
| 480 V | 52.1 A |
Protection and conductors
| Side | Current | Breaker (125%) | Copper (75 °C) | Aluminum (75 °C) |
|---|---|---|---|---|
| Primary 480 V | 52.1 A | 70 A | 4 AWG | 3 AWG |
| Secondary 240 V | 104.2 A | 150 A | 1/0 AWG | 3/0 AWG |
450.3(B) with primary and secondary protection. Secondary conductors also follow the tap rules in 240.21(C).