Kilowatts to amps calculator

Choose the system and enter the value. The result includes the copper wire that carries the current.

V
%

Result

Fill in the circuit, then press the button.

Formula

I = kW × 1,000 ÷ (V × PF), or ÷ (1.732 × V × PF) for three-phase

Power factor is 1 for resistive loads such as heaters and incandescent lights, and about 0.8 to 0.95 for motors and electronics. Leave it at 1 if you don't know it and the load is mostly heat.

Chart

kW120 V240 V208 V 3φ480 V 3φ
1 kW8.3 A4.2 A2.8 A1.2 A
2 kW16.7 A8.3 A5.6 A2.4 A
5 kW41.7 A20.8 A13.9 A6.0 A
7.5 kW62.5 A31.2 A20.8 A9.0 A
10 kW83.3 A41.7 A27.8 A12.0 A
15 kW125.0 A62.5 A41.6 A18.0 A
20 kW166.7 A83.3 A55.5 A24.1 A
25 kW208.3 A104.2 A69.4 A30.1 A
50 kW416.7 A208.3 A138.8 A60.1 A
100 kW833.3 A416.7 A277.6 A120.3 A

Power factor 1.

Common questions

Do I use 1.732 for three-phase?

Yes. In balanced three-phase power, P = 1.732 × V(line to line) × I × PF.