112.5 kVA transformer sizing

A 112.5 kVA three-phase transformer carries 312 A on a 208 V secondary and 135 A on a 480 V primary. Enter your voltages to size breakers and wire.

kVA
V
V

Transformer

Fill in the circuit, then press the button.

Full-load current

VoltageCurrent
208 V312.3 A
240 V270.6 A
480 V135.3 A
600 V108.3 A

Protection and conductors

SideCurrentBreaker (125%)Copper (75 °C)Aluminum (75 °C)
Primary 480 V135.3 A175 A2/0 AWG4/0 AWG
Secondary 208 V312.3 A400 A600 kcmilparallel sets

450.3(B) with primary and secondary protection. Secondary conductors also follow the tap rules in 240.21(C).

Common questions

How many amps is a 112.5 kVA transformer?

312.3 A at 208 V and 135.3 A at 480 V, three-phase.