Voltage Drop Calculator

HomeConversions

30 kVA transformer sizing

A 30 kVA three-phase transformer carries 83 A on a 208 V secondary and 36 A on a 480 V primary. Enter your voltages to size breakers and wire.

kVA
V
V

Transformer

Fill in the circuit, then press the button.

Full-load current

VoltageCurrent
208 V83.3 A
240 V72.2 A
480 V36.1 A
600 V28.9 A

Protection and conductors

SideCurrentBreaker (125%)Copper (75 °C)Aluminum (75 °C)
Primary 480 V36.1 A50 A8 AWG6 AWG
Secondary 208 V83.3 A110 A2 AWG1/0 AWG

450.3(B) with primary and secondary protection. Secondary conductors also follow the tap rules in 240.21(C).

Common questions

How many amps is a 30 kVA transformer?

83.3 A at 208 V and 36.1 A at 480 V, three-phase.

Sources

  • NFPA 70, National Electrical Code, 2023 edition (https://www.nfpa.org/codes-and-standards/nfpa-70-standard-development/70)