Enter up to four groups of THHN/THWN-2 wires. The calculator totals their area, applies the Chapter 9 fill limit and shows every trade size.

Conduit size

Fill in the circuit, then press the button.

Fill limits

WiresMaximum fill
153%
231%
3 or more40%
Nipple 24 in or less60%

Chapter 9, Table 1 and Note 4.

THHN conductor areas

SizeArea
14 AWG0.0097 in²
12 AWG0.0133 in²
10 AWG0.0211 in²
8 AWG0.0366 in²
6 AWG0.0507 in²
4 AWG0.0824 in²
3 AWG0.0973 in²
2 AWG0.1158 in²
1 AWG0.1562 in²
1/0 AWG0.1855 in²
2/0 AWG0.2223 in²
3/0 AWG0.2679 in²
4/0 AWG0.3237 in²
250 kcmil0.397 in²
300 kcmil0.4608 in²
350 kcmil0.5242 in²
400 kcmil0.5863 in²
500 kcmil0.7073 in²

Chapter 9, Table 5.

Common questions

Does the ground wire count for conduit fill?

Yes. Every conductor in the raceway, including equipment grounds and bonding jumpers, counts toward fill.