Conduit fill calculator
Enter up to four groups of THHN/THWN-2 wires. The calculator totals their area, applies the Chapter 9 fill limit and shows every trade size.
Conduit size
Fill in the circuit, then press the button.
Fill limits
| Wires | Maximum fill |
|---|---|
| 1 | 53% |
| 2 | 31% |
| 3 or more | 40% |
| Nipple 24 in or less | 60% |
Chapter 9, Table 1 and Note 4.
THHN conductor areas
| Size | Area |
|---|---|
| 14 AWG | 0.0097 in² |
| 12 AWG | 0.0133 in² |
| 10 AWG | 0.0211 in² |
| 8 AWG | 0.0366 in² |
| 6 AWG | 0.0507 in² |
| 4 AWG | 0.0824 in² |
| 3 AWG | 0.0973 in² |
| 2 AWG | 0.1158 in² |
| 1 AWG | 0.1562 in² |
| 1/0 AWG | 0.1855 in² |
| 2/0 AWG | 0.2223 in² |
| 3/0 AWG | 0.2679 in² |
| 4/0 AWG | 0.3237 in² |
| 250 kcmil | 0.397 in² |
| 300 kcmil | 0.4608 in² |
| 350 kcmil | 0.5242 in² |
| 400 kcmil | 0.5863 in² |
| 500 kcmil | 0.7073 in² |
Chapter 9, Table 5.
Common questions
Does the ground wire count for conduit fill?
Yes. Every conductor in the raceway, including equipment grounds and bonding jumpers, counts toward fill.