Voltage Drop Calculator

HomeCode tools

PVC conduit fill chart

PVC has thicker walls than EMT, so the same trade size holds fewer wires, and Schedule 80 holds fewer still.

PVC size

Fill in the circuit, then press the button.

Schedule 40

Trade size14121086421/0
1/2 in118531110
3/4 in2115954111
1 in34251596431
1-1/4 in6043271611753
1-1/2 in8259372115974
2 in1359962362616117
2-1/2 in193141895137221610
3 in2992181377957352515
3-1/2 in40129318410677473321
4 in51737723813799614327

Maximum THHN/THWN-2 conductors of one size in PVC Schedule 40, from Chapter 9, Tables 1, 4 and 5, with the Note 7 rounding rule.

Schedule 80

Trade size14121086421/0
1/2 in96411100
3/4 in1712743111
1 in28201375311
1-1/4 in513723139642
1-1/2 in7051321813863
2 in1188654312214106
2-1/2 in17012478453220149
3 in2651931227051312214
3-1/2 in3582611649568423018
4 in46433821312389543924

Maximum THHN/THWN-2 conductors of one size in PVC Schedule 80, from Chapter 9, Tables 1, 4 and 5, with the Note 7 rounding rule.

Common questions

When is Schedule 80 required?

Where PVC is exposed to physical damage, such as where it rises out of the ground along a driveway (352.10(F)).

Sources

  • NFPA 70, National Electrical Code, 2023 edition (https://www.nfpa.org/codes-and-standards/nfpa-70-standard-development/70)