150 kVA transformer sizing
A 150 kVA three-phase transformer carries 416 A on a 208 V secondary and 180 A on a 480 V primary. Enter your voltages to size breakers and wire.
Transformer
Fill in the circuit, then press the button.
Full-load current
| Voltage | Current |
|---|---|
| 208 V | 416.4 A |
| 240 V | 360.9 A |
| 480 V | 180.4 A |
| 600 V | 144.3 A |
Protection and conductors
| Side | Current | Breaker (125%) | Copper (75 °C) | Aluminum (75 °C) |
|---|---|---|---|---|
| Primary 480 V | 180.4 A | 250 A | 250 kcmil | 350 kcmil |
| Secondary 208 V | 416.4 A | 600 A | parallel sets | parallel sets |
450.3(B) with primary and secondary protection. Secondary conductors also follow the tap rules in 240.21(C).
Common questions
How many amps is a 150 kVA transformer?
416.4 A at 208 V and 180.4 A at 480 V, three-phase.