225 kVA transformer sizing

A 225 kVA three-phase transformer carries 625 A on a 208 V secondary and 271 A on a 480 V primary. Enter your voltages to size breakers and wire.

kVA
V
V

Transformer

Fill in the circuit, then press the button.

Full-load current

VoltageCurrent
208 V624.6 A
240 V541.3 A
480 V270.6 A
600 V216.5 A

Protection and conductors

SideCurrentBreaker (125%)Copper (75 °C)Aluminum (75 °C)
Primary 480 V270.6 A350 A500 kcmil750 kcmil
Secondary 208 V624.6 A800 Aparallel setsparallel sets

450.3(B) with primary and secondary protection. Secondary conductors also follow the tap rules in 240.21(C).

Common questions

How many amps is a 225 kVA transformer?

624.6 A at 208 V and 270.6 A at 480 V, three-phase.