75 kVA transformer sizing
A 75 kVA three-phase transformer carries 208 A on a 208 V secondary and 90 A on a 480 V primary. Enter your voltages to size breakers and wire.
Transformer
Fill in the circuit, then press the button.
Full-load current
| Voltage | Current |
|---|---|
| 208 V | 208.2 A |
| 240 V | 180.4 A |
| 480 V | 90.2 A |
| 600 V | 72.2 A |
Protection and conductors
| Side | Current | Breaker (125%) | Copper (75 °C) | Aluminum (75 °C) |
|---|---|---|---|---|
| Primary 480 V | 90.2 A | 125 A | 1 AWG | 2/0 AWG |
| Secondary 208 V | 208.2 A | 300 A | 350 kcmil | 500 kcmil |
450.3(B) with primary and secondary protection. Secondary conductors also follow the tap rules in 240.21(C).
Common questions
How many amps is a 75 kVA transformer?
208.2 A at 208 V and 90.2 A at 480 V, three-phase.