Voltage Drop Calculator

HomeConversions

45 kVA transformer sizing

A 45 kVA three-phase transformer carries 125 A on a 208 V secondary and 54 A on a 480 V primary. Enter your voltages to size breakers and wire.

kVA
V
V

Transformer

Fill in the circuit, then press the button.

Full-load current

VoltageCurrent
208 V124.9 A
240 V108.3 A
480 V54.1 A
600 V43.3 A

Protection and conductors

SideCurrentBreaker (125%)Copper (75 °C)Aluminum (75 °C)
Primary 480 V54.1 A70 A4 AWG3 AWG
Secondary 208 V124.9 A175 A2/0 AWG4/0 AWG

450.3(B) with primary and secondary protection. Secondary conductors also follow the tap rules in 240.21(C).

Common questions

How many amps is a 45 kVA transformer?

124.9 A at 208 V and 54.1 A at 480 V, three-phase.

Sources

  • NFPA 70, National Electrical Code, 2023 edition (https://www.nfpa.org/codes-and-standards/nfpa-70-standard-development/70)